ED 15062-7 • MICROTECH II CHILLER CONTROLLER 30
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Chiller Mode Output
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the current operating mode of the chiller. (I19)
Measurement
Units
Data Type
Valid Range
Default Value
HVAC Mode
NA
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
See Below
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Input
13
44
Present Value
85
Object Name
ActiveMode
Property Values
1. ICE
2. COOL
3. HEAT
LONWORKS
The LONWORKS equivalent of this data point is part of the Chiller Status network output variable (see
).
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerStat
Chiller
chlr_status
127
3 bytes