14
ED 15121
48483=COMP SHUTDOWN–No Pressure Change After Start
Circuit #3
48515=COMP SHUTDOWN–No Pressure Change After Start
Circuit #4
48675=COMP SHUTDOWN–No Pressure at Startup Circuit
#1
48707=COMP SHUTDOWN–No Pressure at Startup Circuit
#2
48739=COMP SHUTDOWN–No Pressure at Startup Circuit
#3
48771=COMP SHUTDOWN–No Pressure at Startup Circuit
#4
48935=COMP SHUTDOWN-Slide position sensor fault
Circuit #1, Comp#1
48967=COMP SHUTDOWN-Slide position sensor fault
Circuit #2, Comp#1
48999=COMP SHUTDOWN-Slide position sensor fault
Circuit #3, Comp#1
49031=COMP SHUTDOWN-Slide position sensor fault
Circuit #4, Comp#1
49155=UNIT
STOP–Emergency Stop Alarm
49411=UNIT STOP–Evaporator Water Temps Inverted
49667=UNIT STOP–External Alarm
49923=Evaporator Leaving Water Temp 1 Sensor Fault
50179=Evaporator Leaving Water Temp 2 Sensor Fault
50435=CIRCUIT SHUTDOWN-Evaporator 1 Freeze
Protection
50691=CIRCUIT SHUTDOWN-Evaporator 2 Freeze
Protection
*Chiller Mode Setpoint – Network (2)
22
34
R/W
0=Null, 1=Ice, 2=Cool, 3=Heat, 4=Cool/Heat Recovery.
The
MicroTech III Chiller only supports Ice and Cool modes. If any
other mode is written, the chiller will be set to Cool mode.
*Cool Setpoint – Network (9)
24
35
R/W
24.98-60.08
°
F (-3.9-15.6
°
C) Default = 43.88
°
F (6.6°C)
Ice Setpoint - Network
26
36
R/W
15.08°-38.12°F (-9.4°-3.4°C)
Default = 24.98°F (-3.9°C)
*Capacity Limit Setpoint - Network (10)
20
38
R/W
0 - 100%
*Boldface indicates data points required for typical minimum integration.
Table 5. Circuit Data Points
Network Control Property
Page
Holding
Register
(4xxxx)
Read/
Write
Description
Circuit #1
Condenser Refrigerant Pressure
24
39
R
0-410 psi (700 psi for R410A)
0-2827 kPa, (4826 kPa for R410A)
Condenser Saturated Refrigerant Temperature
24
40
R
-14.98-185°F (-26.1-85°
C)
Evaporator Refrigerant Pressure
25
41
R
-349.97–349.97 psi (-2413 kPa – 2413 kPa)
Evaporator Saturated Refrigerant Temperature
26
42
R
-14.98-185°F (-26.1-85°
C)
Circuit #2
Condenser Refrigerant Pressure
24
43
R
0-410 psi (700 psi for R410A)
0-2827 kPa, (4826 kPa for R410A)
Condenser Saturated Refrigerant Temperature
24
44
R
-14.98-185°F (-26.1-85°
C)
Evaporator Refrigerant Pressure
25
45
R
-349.97–349.97 psi (-2413 kPa – 2413 kPa)
Evaporator Saturated Refrigerant Temperature
26
46
R
-14.98-185°F (-26.1-85°
C)
Circuit #3
Condenser Refrigerant Pressure
24
47
R
0-410 psi (700 psi for R410A)
0-2827 kPa, (4826 kPa for R410A)
Condenser Saturated Refrigerant Temperature
24
48
R
-14.98-185°F (-26.1-85°
C)
Evaporator Refrigerant Pressure
25
49
R
-349.97–349.97 psi (-2413 kPa – 2413 kPa)
Evaporator Saturated Refrigerant Temperature
26
50
R
-14.98-185°F (-26.1-85°
C)
Circuit #4
Condenser Refrigerant Pressure
24
51
R
0-410 psi (700 psi for R410A)
0-2827 kPa, (4826 kPa for R410A)
Condenser Saturated Refrigerant Temperature
24
52
R
-14.98-185°F (-26.1-85°
C)
Evaporator Refrigerant Pressure
25
53
R
-349.97–349.97 psi (-2413 kPa – 2413 kPa)
Evaporator Saturated Refrigerant Temperature
26
54
R
-14.98-185°F (-26.1-85°
C)