8
AGZ 025D through 190D
OMM 1087
Table 7, Capacity and Power Derates, Models AGZ 140D to 190D
Fouling Factor
Chilled Water
Delta T
0.0001 (0.0176)
0.00025 (0.044)
0.00075 (0.132)
0.00175 (0.308)
Altitude
°F °C Cap. Power Cap. Power Cap. Power Cap. Power
6 3.3 0.990 0.997 0.976 0.994 0.937 0.983 0.868 0.964
8 4.4 0.994 0.998 0.981 0.995 0.942 0.984 0.872 0.965
10 5.6 1.000 1.000 0.987 0.996 0.947 0.986 0.877 0.967
12 6.7 1.005 1.001 0.991 0.997 0.951 0.986 0.881 0.968
14 7.7 1.009 1.002 0.995 0.998 0.955 0.987 0.884 0.968
Sea
Level
16 8.9 1.013 1.004 1.000 1.000 0.960 0.989 0.889 0.970
6 3.3 0.987 1.005 0.974 1.002 0.934 0.991 0.865 0.972
8 4.4 0.992 1.006 0.979 1.003 0.940 0.992 0.870 0.973
10 5.6 0.997 1.008 0.984 1.004 0.944 0.994 0.875 0.975
12 6.7 1.002 1.009 0.989 1.005 0.949 0.994 0.879 0.975
14 7.7 1.007 1.011 0.993 1.007 0.953 0.996 0.883 0.977
2000 feet
16 8.9 1.011 1.012 0.998 1.008 0.958 0.997 0.887 0.978
6 3.3 0.985 1.014 0.972 1.010 0.933 0.999 0.864 0.980
8 4.4 0.991 1.015 0.977 1.012 0.938 1.001 0.869 0.981
10 5.6 0.995 1.016 0.982 1.013 0.943 1.002 0.873 0.982
12 6.7 1.000 1.018 0.987 1.014 0.947 1.003 0.877 0.984
14 6.8 1.005 1.019 0.991 1.015 0.951 1.004 0.881 0.985
4000 feet
16 8.9 1.009 1.021 0.995 1.017 0.955 1.006 0.884 0.987
6 3.3 0.982 1.023 0.969 1.020 0.930 1.009 0.861 0.989
8 4.4 0.988 1.025 0.975 1.022 0.935 1.010 0.866 0.991
10 5.6 0.992 1.026 0.979 1.022 0.940 1.011 0.870 0.992
12 6.7 0.997 1.028 0.984 1.024 0.944 1.013 0.875 0.994
14 7.7 1.002 1.029 0.989 1.025 0.949 1.014 0.879 0.995
6000 feet
16 8.9 1.006 1.031 0.992 1.027 0.952 1.016 0.882 0.996
6 3.3 0.979 1.034 0.966 1.031 0.927 1.019 0.859 1.000
8 4.4 0.984 1.036 0.971 1.032 0.932 1.021 0.863 1.002
10 5.6 0.990 1.037 0.976 1.033 0.937 1.022 0.868 1.002
12 6.7 0.993 1.039 0.980 1.035 0.941 1.024 0.871 1.004
14 7.7 0.998 1.041 0.985 1.037 0.945 1.026 0.875 1.006
8000 feet
16 8.9 1.003 1.041 0.990 1.038 0.950 1.026 0.879 1.007
Evaporator Freeze Protection
Evaporator freeze-up can be a concern in the
application of air-cooled water chillers. To
protect against freeze-up, insulation and an
electric heater cable are furnished with the unit.
This protects the evaporator down to -20°F (-
29°C) ambient air temperature. Although the
evaporator is equipped with freeze protection,
it does not protect water piping external to the
unit or the evaporator itself if there is a power
failure or heater cable burnout. Consider the
following recommendations for additional
protection.
1.
If the unit will not be operated during the
winter, drain evaporator and chilled water
piping and flush with glycol. Drain and
vent connections are provided on the
evaporator to ease draining.
2.
Add a glycol solution to the chilled water
system to provide freeze protection.
Freeze point should be approximately ten
degrees below minimum design ambient
temperature.
3.
The addition of thermostatically controlled
heat and insulation to exposed piping.
4.
Continuous circulation of water through
the chilled water piping and evaporator.
The evaporator heater cable is factory wired to
the 115-volt circuit in the control box. This
power should be supplied from a separate
source, but it can be supplied from the control
circuit. Operation of the heater cable is
Summary of Contents for McQuay AGZ-D