MicroTech III Controller Operation
www.DaikinApplied.com 85
IM 991-2 • MAVERICK II ROOFTOP
–
Keypad/Display Menu Structure
Cooling Set-Up
Clg Stage Time= 5min
Clg DB= 2.0°F
Clg Period= 20s
Clg Gain= 1
Clg PAT= 40s
CW Max Chg= 15%
Clg Lo OAT Lk=
55ºF (RTU/SCU)
0°F (MPS)
25°F (DPS or RTU w/
VFD Cmps)
OAT Diff= 2.0°F
Min EWT= 55°F
Clg Reset= None
Min Clg Spt= 55.0°F
Min Clg Spt @= 0/NA
Max Clg Spt= 65.0°F
Max Clg Spt@= 100/NA
Lead Circuit= #1
Staging Type= Std
CFanOut1 Spt= 55°F
CFanOut2 Spt= 65°F
CFanOut3 Spt= 75°F
Cond Fan Diff= 5°F
Unocc Diff= 3°F
DT Above Spt= ________
DT Below Spt= ________
Econo Set-Up
EconChgovr= Enth&DB
Econo FDD= On
Clg Stage Time= 5min
Chgover Temp= 55.0°F
Clg DB= 2.0°F
Econo Period=
30/40s (air/water)
Econo Gain=
1-Oct (air/water)
Econo PAT=
60/40s (air/water)
Econo Max Chg=
10/15% (air/water)
Flush Econo= Yes
Econo Diff= 2.0°F
EWT Diff= 3.0°F
Clg Reset= None
Min Clg Spt= 55.0°F
Min Clg Spt @= 0/NA
Max Clg Spt= 65.0°F
Max Clg Spt@= 100/NA
Max OAT Lmt= 75°F
Min OAT Lmt= 70°F
Calibrate OAD= No
PosSwOpen= 97%
Max Sw Diff= 3%
PosSwClose= 3%
Min SW Diff= 5%
OAD Sw Status= _______
Timer Settings
Service Time= 0min
Start Up= 180s
Recirculate= 180s
Zero OA Time= 0min
Tnt Override= 120min
Post Heat= 0s
Pwd Timeout= 10min
Low DAT= 6min
ClgStateDelay= 300s
Bypass Valve= 300s
Clg Stg Time= 5min
Htg Stg Time= 5min
Air Flw Ign= 120s
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
EvCnd Stg Tm= 10min
WRV Init Tm= 60s
Min WRV Time= 60s
Htg Wrmup Tm= 240s
Htg Hld Period= 240s
RH Srg Time= 10min
Srvc Time Inc= 20s
OffHtCIDelay= 120s
Unit Set-Up
Apply Changes= No
RAT Sensor= Yes
OAT Sensor= Yes
Space Sensor= Digtl/Net
Eng Units= English
Unit Name= xxxxxxxxxxxx
Rapid Start= No
Rapid Start Tm= 10min
DO10 Clg= FanOp
SAF Set-Up
SAF Ctrl= DSP
CO
2
CONTROL
BSP CONTROL
AplyInputChgs= No
Min PPM= 0PPM
BSP DB= 0.01in
CO2 Input= None
Max PPM= 2000PPM
BSP Period= 5s
CFM Input= None
V/A @ Min PPM= 0V
BSP Gain= 0.2
BSP Input= No
V/A @ Max PPM= 10V
Max Spd Chg= 4%
SPEED CONTROL
Min SAF PPM= 800PPM
SAF SETUP
Rem SAF Cap= 33%
Max SAF PPM= 1100PPM
SAF Ctrl Dly= 30s
DSP CONTROL
Min PPM Spd= 50%
Min Speed= 33%
DSP DB= 0.1in
Max PPM Spd= 100%
VAVBox Out= _________
VFD Ramp Time= 60s
CFM CONTROL
Max SAF Hz=
Min Period= 5s
Min CFM= 0CFM
Max Vent Speed= 100%
Max Spd Chg= 15%
Max CFM= 10000CFM
Max SAF RPM= 2600
Duct Press 1= X.Xin
V/A @ Min CFM= 0V
ECM Status= __________
Duct Press 2= X.Xin
V/A @ Max CFM= 10 V
1 ZONE VAV CONTROL
SAF CFM DB= 3%
Min Clg Spd= 40%
SAF CFM Period= 30s
Max Clg Spd= 100%
SAF CFM Gain= 0.1
Min Htg Spd= 40%
SAF CFM MxChg= 5%
Max Htg Spd= 100%
Space Period= 60s
Space Gain= 0.8
Space PAT= 400s
Space Max Chg= 10%
Htg/Clg ChgOvr Set-Up
Ctlr Temp Src= RAT
AplyTstatchg= No
Use Tstat Spt= No
Occ Clg DB= 2.0°F
Clg Period= 60s
Clg Gain= 0.1
Clg PAT= 600s
Max Clg Chg= 5.0°F
Occ Htg DB= 2.0°F
Htg Period= 60s
Htg Gain= 0.1
Htg PAT= 600s
Max Htg Chg= 5.0°F
CalDRemSpt@10°C= No
CalDRemSpt@50°F= No
CalDRemSpt@30°C= No
CalDRemSpt@86°F= No
DemandShed= Ena
ClgDmdShdInc= 4°F
HtgDmdShdInc= 4°F
ClgShedRate= 2.0°F/hr
HtgShedRate= 2.0°F/hr
RF/EF Set-Up
RF/EF Ctrl= Tracking
MinExStrtTm= 120s
Rem RAF Cap= 5%
MinExStopTm= 120s
Rem ExhF Cap= 5%
MinExOAPos= 5%
BSP DB= 0.01in
MinExSAFCap= 10%
BSP Period= 5s
ExhOnOAPos= 40%
BSP Gain= 0.2s
ExhMxOAPos= 100%
Max Spd Chg= 4%
Exh Stg 1 On= 40%
Sup Fan Max= 100%
Exh Stg 1 Off= 30%
RF @ SF Max= 95%
Exh Stg 2 On= 55%
Sup Fan Min= 30%
Exh Stg 2 Off= 40%
RF @ SF Min= 25%
Exh Stg 3 On= 70%
Lo Fan Diff= 75%
Exh Stg 3 Off= 50%
Hi Fan Diff- 75%
Max RF/EF Hz= 60Hz
RFEF Ctrl Dly= 30s
Max Vent Spd= 100%
Min Speed=
5% (with Exhaust Fan)
33% (with Return Fan)
Max RFEF RPM= 2600
ECM Status= _________
Compressor Limiting
Clg Press Lmtg=_______
Htg Press Lmtg=_______
C Ratio Lmtg=_________
Ref DLT Lmtg=_________
INV Brd Lmtg=_________
INV Man Dsbl= Enable
Comp3 ManDsbl= Enable
Date/Time
MM/DD/YYYY HH:MM:SS
INV Cmp Set-Up
COMPRESSOR STATUS
COMPRESSOR SETUP
Clg State= ____________
Clg Lo OAT Lk=
55°F (RTU/SCU)
0°F (MPS)
25°F (DPS)
Htg State= ____________
INV Cmp Spd= XXX.X%
INV Spd Cmd= XXX.X%
Comp 3=_____________
Htg Lo OAT Lk=
0.0ºF
45°F (100% OA w/o ER)
Prev Standby=_______
►
Compressor Limiting
►
Fault Code Details
►
Htg Hi OAT Lk= 55.0ºF
INV Port Temp= XXX.XºF
EffHtgOATLk= _______ºF
INV Fin Temp= XXX.XºF
OAT Diff= 2ºF
INV Cmp Amps= XX.XA
INV Period= 20s
REFRIG CIRCUIT STATUS
INV Gain= 2.5
PTD= XXX.Xpsi
INV PAT= 10s
PTS= XXX.Xpsi
INV Max Chg= 15%
4 Way Valve=__________
IFB COMM STATUS
►
RcvrSol Valve=_________
BP Sol Valve=_________
1
2
Commission Unit
Unit Set-Up
►
Timer Settings
►
SAF Set-Up
►
RF/EF Set-Up
►
Htg/Clg ChgOvr Set-Up
►
Cooling Set-Up
►
INV Cmp Set-Up
►
Var Cmp Set-Up
►
Econo Set-Up
►
Min OA Set-Up
►
Heating Set-Up
►
OA Fan Set-Up
►
Exp Valve Set-Up
►
Defrost Set-Up
►
Dehum Set-Up
►
Energy Rec Set-Up
►
Head Pressure Set-Up
►
Evap Cond Set-Up
►
D3 Set-Up
►
Alarm Configuration
►
Var Comp Set-Up
COMPRESSOR STATUS
Var Cmp Status= _______
Var Spd Cmd= _________
Comp 1= _____________
Comp 3= _____________
Comp 5= _____________
REFRIG CIRCUIT STATUS
PTD1= _______________
PTD2= _______________
VCmpDischSH= _______
C1DschSatTmp= _______
C2DschSatTmp= _______
DRT1= _______________
DRT2= _______________
Cond Sol 1= Off
Cond Sol 2= Off
COMPRESSOR SET-UP
Var Cmp Period= 20s
Var Cmp Gain= 1
Var Cmp PAT= 40s
VarCmp MaxChg= 10%
OilBoost= Off
LowOilTime= 10min
OilBoostTime= 15min
LowTcOAT= 80°F
Min OA Set-Up
AplyMinOAChg= No (Uses
MinOAT Type Instance Name)
CFM RESET
FAN SPEED RESET
OA Flow= XXXXXCFM
Min Fan Diff= 20%
Min OA Reset= None
MinOAFlwSpt= 2000CFM
Max Fan Diff= 50%
BSPOAOvrd= No
Field Stn Rst= No
Min Clg Spd= 40%
RstLmtSnsr= None
Field Stn Cfg= VDC
Des Clg Spd= 100%
EXTERNAL RESET
Min CFM= 0 CFM
BSP RESET
OA @ MinV/mA= 0%
Max CFM= 10000 CFM
MinRFEFTm= 120s
OA @ MaxV/mA= 100%
V/A @Min CFM= 0.0/V
BSP OvdST= 5s
Min V/mA= 0.0/V
V/A @Max CFM= 10.0/V
BSP OvdGain= 0.2
Max V/mA= 10.0/V
OA CFM DB= 3%
BSP OvdMaxChg= 4%
CO
2
RESET
OA CFM Period= 30s
DAMPER LIMITING
IAQ Reset= Yes
OA CFM Gain= 0.1
RstTLmt= 32.0ºF
PPM@DCVLmt= 800PPM
OA CFM Max Chg= 5%
RstTSmplTm= 5s
PPM@VntLmt= 1000PPM
Design Flow= Yes
RstTGain= 0.2
IAQ PPM= XXXXPPM
Des Flo DB= 3%
RstPAT= 60s
Min PPM= 0 PPM
DF Period= 30s
RstTMaxChg= 4%
Max PPM= 2000 PPM
Des Flo Gain= 0.1
0–30% OA Max= 30%
V/A @Min PPM= 0.0/V
DF Max Chg= 5%
Min Inc Rate= 0.03
V/A @Max PPM= 10.0/V
RH Lvl Pos= ____________
Max Inc Rate= 1.0
LH Lvl Pos= ____________
1
,
2
See the expansion
information on page 91
List continues
on, page 86