ELECTRICAL DATA
Main Breakers
Figure 19: Main Breakers
VFD Size
SCCR
Breaker
Frame Size
Trip Unit
LUG
FRN5200
35 kAIC
EATON 600 AMP, 600 TRIP SETTING
LD3600F
LES3600LSI
(2) 3TA603LDK
FRN5200
65 kAIC
EATON 600 AMP, 600 TRIP SETTING
HLD3600F
LES3600LSI
(2) 3TA603LDK
FRN5200
100 kAIC
EATON 600 AMP, 600 TRIP SETTING
LDC3600F
LES3600LSI
(2) 3TA603LDK
FRN5900
35 kAIC
EATON 800 AMP, 700 TRIP SETTING
MDL3800F
MES3800LSI
(6) TA800MA2
FRN5900
65 kAIC
EATON 800 AMP, 700 TRIP SETTING
HMDL3800F
MES3800LSI
(6) TA800MA2
FRN5900
100 kAIC
EATON 800 AMP, 700 TRIP SETTING
NGC312032E
MES3800LSI
(6) TA800MA2
FRN6500
35 kAIC
EATON 800 AMP, 800 TRIP SETTING
MDL3800F
MES3800LSI
(6) TA800MA2
FRN6500
65 kAIC
EATON 800 AMP, 800 TRIP SETTING
HMDL3800F
MES3800LSI
(6) TA800MA2
FRN6500
100 kAIC
EATON 1200 AMP, 800 TRIP SETTING
NGC312032E
MES3800LSI
(6) TA800MA2