24.3.1 Error codes: Overview
In case other error codes appear, contact your dealer.
Main code
LRYEN10* LRNUN5* Cause
Solution
O
O
Electrical leakage
Correct the field wiring and connect
ground wiring.
O
—
Stop valves are closed.
Open the stop valve on both the gas
and liquid side.
O
O
Malfunction of fan motor
For LRYEN10*:
▪
(M1F) - A9P (X1A)
▪
(M2F) - A10P (X1A)
▪
(M3F) - A11P (X1A)
For LRNUN5*:
▪
(M1F) - A4P (X1A)
Check connection on PCB or
actuator.
O
O
Malfunction of electronic expansion
valve coil
For LRYEN10*:
▪
(Y7E) - A12P (X8A)
▪
(Y4E) - A12P (X9A)
▪
(Y14E) - A12P (X10A)
▪
(Y3E) - A1P (X21A)
▪
(Y8E) - A1P (X22A)
▪
(Y2E) - A1P (X23A)
▪
(Y1E) - A1P (X25A)
▪
(Y13E) - A1P (X26A)
▪
(Y5E) - A2P (X21A)
▪
(Y16E) - A2P (X22A)
▪
(Y17E) - A2P (X23A)
For LRNUN5*:
▪
(Y3E) - A1P (X21A)
▪
(Y1E) - A1P (X22A)
▪
(Y4E) - A1P (X23A)
▪
(Y2E) - A1P (X24A)
Check connection on PCB or
actuator.
O
—
Wrong selection of cooling load
(including the expansion valves)
Reselect the cooling load, including
the expansion valve.
O
O
Malfunction of ambient
temperature sensor
For LRYEN10* and LRNUN5*:
▪
(R1T) - A1P (X18A)
Check connection on PCB or
actuator.