Troubleshooting
18.1
Solving problems based on error
codes
If the unit runs into a problem, the user interface displays an error
code. It is important to understand the problem and to take
measures before resetting an error code. This should be done by a
licensed installer or by your local dealer.
This chapter gives you an overview of all possible error codes and
their descriptions as they appear on the user interface.
For detailed troubleshooting of each error, see the service manual.
18.1.1
Error codes: Overview
In case other error codes appear, contact your dealer.
Main code
LRYEN10*
LRNUN5*
Cause
Solution
O
O
Electrical leakage
Correct the field wiring and connect ground
wiring.
O
—
The stop valves are closed
Open the stop valve on both the gas and
liquid side.
O
O
Malfunction of fan motor
For LRYEN10*:
▪ (M1F) - A9P (X1A)
▪ (M2F) - A10P (X1A)
▪ (M3F) - A11P (X1A)
For LRNUN5*:
▪ (M1F) - A4P (X1A)
Check connection on PCB or actuator.
O
O
Malfunction of electronic expansion valve coil
For LRYEN10*:
▪ (Y7E) - A12P (X8A)
▪ (Y4E) - A12P (X9A)
▪ (Y14E) - A12P (X10A)
▪ (Y3E) - A1P (X21A)
▪ (Y8E) - A1P (X22A)
▪ (Y2E) - A1P (X23A)
▪ (Y1E) - A1P (X25A)
▪ (Y13E) - A1P (X26A)
▪ (Y5E) - A2P (X21A)
▪ (Y16E) - A2P (X22A)
▪ (Y17E) - A2P (X23A)
For LRNUN5*:
▪ (Y3E) - A1P (X21A)
▪ (Y1E) - A1P (X22A)
▪ (Y4E) - A1P (X23A)
▪ (Y2E) - A1P (X24A)
Check connection on PCB or actuator.
O
—
Wrong selection of cooling load (including the
expansion valves)
Reselect the cooling load, including the
expansion valve.
O
O
Malfunction of ambient temperature sensor
For LRYEN10* and LRNUN5*:
▪ (R1T) - A1P (X18A)
Check connection on PCB or actuator.