iTM plus adaptor
Model
DCM601A72
Installation Manual
Page 1: ...iTM plus adaptor Model DCM601A72 Installation Manual ...
Page 2: ...ful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiv...
Page 3: ...ious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices NOTE Indicates situations that may result in equipment or prop erty damage accidents only WARNING Only qualified personnel must carry out the installation work Consult your Daikin dealer regarding relocation and reinstalla...
Page 4: ... Near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction d Where flammable gas may leak where there is carbon fiber or ignitable dust suspensions in the air or where volatile flammables such as thinner or gaso line are handled Operating the unit in such conditions can cause a fire e High temperature area ...
Page 5: ...inal location and schematic wiring diagram 16 2 2 2 Wiring specifications 17 2 2 3 Precautions for using multiple centralized controllers 17 2 3 Connecting an emergency stop input device or power meter 18 2 3 1 Terminal location and schematic wiring diagram 19 2 3 2 Wiring specifications 19 2 4 Connecting power supply 20 2 4 1 Terminal location and schematic wiring diagram 20 2 4 2 Wiring specific...
Page 6: ...DCM601A72 iTM plus adaptor English 5 Quick Operation Guide 30 5 1 Viewing target area and management point information in list format 30 5 2 Displaying areas and management points 30 5 3 Starting stopping an area or management point 31 ...
Page 7: ...t an appropriate space for installing the iTM plus adaptor is available 1 1 Checking that all accessories are included Based on the following accessory list check that all accessories for the iTM plus adaptor are included If there is any missing or defective part contact your DAIKIN dealer where you purchased the product Accessories included with iTM plus adaptor A B C D d 1 a 1 b 1 c 1 A a 1 iTM ...
Page 8: ...rrangement of terminals and switches on the unit and draw up an effi cient work plan For connection details including the cable type terminal size and wiring precautions refer to 2 Electric wiring 1 3 1 Front face All the terminals used during installation are located on the front face of the iTM plus adaptor The power supply terminal is protected with a cover for safety Remove the screw to detach...
Page 9: ...or For each iTM plus adaptor set a unique number between 2 to 8 G TERM The switch used to activate the termination resistor of the terminal iTM plus adaptor in the connection with other iTM plus adaptor or the intelligent Touch Man ager using the plus ADP IF terminal Factory default OFF H DIII MASTER The switch for setting MASTER or SLAVE for the iTM plus adaptor when there are multiple DIII NET c...
Page 10: ...ermining installation place Be sure to install the iTM plus adaptor in a place that meets the conditions described in 1 4 1 to 1 4 3 1 4 1 Installation place and mounting direction Below are the description of the installation place and mounting direction Be sure to confirm Installation place Indoor inside control enclosure which must be lockable or designed to be opened only with a special tool M...
Page 11: ...d for installation Make sure that there is a minimum clearance of 25 32 in between each unit and wiring ducts Multiple iTM plus adaptors can be installed without clearance in the horizontal direction Installation space required for iTM plus adaptor Required installa tion space 1 9 16 1 9 16 25 32 25 32 25 32 in A A 6 5 16 5 7 8 A Wiring duct ...
Page 12: ...nnecting DIII NET compatible air conditioning equipment 2 4 Connecting power supply Equipment spe cific procedures 2 3 Connecting an emergency stop input device or power meter WARNING Do not turn on the power supply before all wire connections are completed Not doing so may cause an electric shock After the wiring is completed double check that all wires are connected cor rectly before turning on ...
Page 13: ...larity Be sure to connect the positive wire to the terminal and the negative wire to the termi nal Also connect the intelligent Touch Manager to the termination of the wiring Terminal location and schematic wiring diagram A intelligent Touch Manager For details refer to the intelligent Touch Manager Installation Manual EM11A018 B iTM plus adaptor C plus ADP IF intelligent Touch Manager D plus ADP ...
Page 14: ...ptor which is the farthest from the intelligent Touch Manager To set the termination resistor change the position of the TERM switch on the front face of the iTM plus adaptor to ON position plus ADP ADDRESS switch and TERM switch NOTE If the two LEDs CPU ALIVE and ALARM both light up during power on after installa tion there is a possibility of a problem with the address assignment An invalid addr...
Page 15: ...Touch Manager can be connected with a maximum of seven iTM plus adaptors you can control a total of 512 groups of air conditioners at a maximum using a single intelligent Touch Manager WARNING Be sure to perform the operation during power off conditions Not doing so may cause an electric shock The maximum length of adhered wiring of high current electrical line of power wires and weak current line...
Page 16: ...these terminals results in a failure of the air conditioner or iTM plus adaptor Schematic diagram of wiring between air conditioning equipment F2 F1 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 E F A B C D D D D D A B C D D D D D A Outdoor unit B OUT OUT communication terminal C IN OUT communication ...
Page 17: ...g length is 3280 ft and total wiring length is 6561 ft or less When using a shielded wire the total wiring length is limited to 4921 ft or less 2 2 3 Precautions for using multiple centralized controllers The centralized controller refers to the equipment e g the intelligent Touch Manager that control multiple air conditioners Besides the intelligent Touch Manager the DAIKIN s product portfolio in...
Page 18: ...entralized controllers that cannot be connected to the same network as the iTM plus adaptor CALCULATE UNIT intelligent Processing Unit Parallel Interface Intelligent Touch Controller DIII NET Plus Adapter Residential Central Remote Controller Schedule Timer Wiring Adaptor for Electrical Appendices 1 KRP2 2 3 Connecting an emergency stop input device or power meter The iTM plus adaptor can perform ...
Page 19: ...o you can use either of them However you can connect up to two wires simultaneously to each COM terminal When using an open collector type output con nect the COM terminal to the negative side Di1 Di2 COM Di3 Di4 COM 2 3 2 Wiring specifications Cable type CPEV cable Core thickness AWG22 19 Cable length 656 ft or less Pulse width A B A Pulse width 20 to 400 ms B Pulse interval 100 ms or more CAUTIO...
Page 20: ...ion terminals are covered with a protective cover Remove this cover before you start connecting the power supply Take out the screw using a Phillips screwdriver to remove the cover After connecting the power supply attach the cover back to its original position Next connect the power supply to the three terminals L Live N Neutral and ground in the POWER section Perform the grounding work without f...
Page 21: ...g on off the earth leakage breaker turns on off the power supply to the iTM plus adaptor When using an earth leakage breaker make sure to select one useful for to protection against overcurrent and short circuit When using an earth leakage breaker only for earth device make sure to use a wiring interrupter together The power supply requires earth leakage breaker installation and earth wire connect...
Page 22: ...all the iTM plus adaptor Screw mounting to control enclosure DIN rail mounting 3 1 Screw mounting to control enclosure 3 1 1 Installation procedure Secure the iTM plus adaptor to the control enclosure using the supplied round head wood screws When done remove the blue protective film from the upper portion of the unit body Mounting to control enclosure ...
Page 23: ...ing to DIN rail Do not use screws to secure the iTM plus adaptor onto the DIN rail Place the iTM plus adaptor over the top of the DIN rail so that the upper hook 1 on the rear face is hooked and push it in direction 3 until the lower hook 2 snaps into the DIN rail When done remove the blue protective film from the upper portion of the unit body 3 3 1 1 2 2 ...
Page 24: ...stallation Manual 3P291714 4B DCM601A72 iTM plus adaptor English 3 2 1 Removal from DIN rail Pull down the lever at the lower portion of the iTM plus adaptor 1 and pull the unit body 2 out toward you 1 1 2 2 ...
Page 25: ... both units are powered on You cannot perform address settings for air conditioners without turning on the power supply For how to set the address for the Ventilator Heat Reclaim Ventilator or differ ent adapters such as a universal adapter refer to the manuals supplied with those devices 4 1 Names of buttons and display areas The names of buttons and areas of a wired remote controller used in thi...
Page 26: ... change the value shown in the parameter number display area to 00 In the address display area the current address setting is displayed This area will show if no address is set Step 2 SETTING GROUP NOTE If the power is not supplied for the intelligent Touch Manager or iTM plus adaptor you cannot change the value to 00 Turn on the power supply for both the intelligent Touch Manager and iTM plus ada...
Page 27: ...ect the address you want to set Step 4 SETTING GROUP 5 Press the SCHEDULE button to make the GROUP indicator stay lit The DIII NET address has been set Step 5 SETTING GROUP 6 Press the Inspection Test Operation button You are now brought back to the screen shown in Step 6 2 Step 6 1 SETTING GROUP Step 6 2 HH F ...
Page 28: ...ced Fan ON Setting Service Settings Error History Outdoor Unit Status Indoor Unit Status 2 3 NOTE If the power is not supplied for the iTM plus adaptor the Group Address menu is not displayed Turn on the power supply for the intelligent Touch Manager and wait for a while before starting the operation It should also be noted that the Group Address menu is not displayed if communica tions between th...
Page 29: ...ase Group Address Group 7 Press the Cancel button three times You are now brought back to the screen shown in Step 7 2 Step 7 1 Gr Addr Set 1 03 Release Group Address Group Step 7 2 Cool Room Thu 82 86 F Set to 35P 5 F 4 1 3 Setting an unique address to each unit when Power Proportional Dis tribution option is used When power distribution is enabled you need to set a unique address for each unit F...
Page 30: ...format A C B List Icon A C A Touch the List button B The screen changes to the list view where selecting Indoor in the Type combo box causes the name operation mode setpoint and fan speed of all areas and indoor units to be listed C Touch the Icon button to return the Icon view screen 5 2 Displaying areas and management points Down Up A B C B C A The level of the current area and management point ...
Page 31: ...n area or management point A On A B B A Select the area or management point you want to start or stop B Select Start or Stop in the On Off buttons When operation is started the icon color changes to green or red depending on the system setting When operation is stopped the color changes to grey ...