background image

DAIKIN 

3P665364-12

T  M22P113B 

DAIKIN ROOM  AIR CONDITIONER 

OPERATION MANUAU 

MODELS: 

F/GTKY50UV16V2 

F/GTKY50UV16U2 

F/GTKY50UV16V39 

F/GTKY50UV16U39 

F/GTKY50UV16V3F 

fC.._JNVERTER> 

3P665364-1

2T  M22P113B

Summary of Contents for GTKY50UV16V2

Page 1: ...DAIKIN 3P665364 12T M22P113B DAIKIN ROOM AIR CONDITIONER OPERATION MANUAU MODELS F GTKY50UV16V2 F GTKY50UV16U2 F GTKY50UV16V39 F GTKY50UV16U39 F GTKY50UV16V3F fC _JNVERTER 3P665364 12T M22P113B...

Page 2: ...ce quality and or longevity of the object concerned Do not exposeplants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that producenaked fla...

Page 3: ...the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop long beep 12 TEMPRATURE DISPLAY 13 OPERA...

Page 4: ...AN 9 ECONO button ECONO operation 10 COANDA button COANDA operation 11 TIMER CANCEL button Cancels the timer setting 12 ONTIMER button 13 OFF TIMER button 14 GOOD SLEEP DISPLAY BUTTON NOTE Notes on re...

Page 5: ...get it wet The maximum transmission distance is about 7m A J P Receiver To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching...

Page 6: ...e remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 c Defau...

Page 7: ...s children from operating the remote controller by mistake To set the CHILD LOCK Press nd ogether for about 5 seconds we will be displayed on the remote LCD If a button is pressed while CHILD LOCK is...

Page 8: ...he LCD The flaps horizontal blades will begin to swing To set the flaps at desired position This function is effective while the flaps are in auto swing mode Press lswiN when the flaps reach the desir...

Page 9: ...the settings to be cancelled and disappears from the LCD ECONO operation functions in COOL and DRY operation POWER CHILL and ECONO operation cannot be used at the same time l fl is displayed on the L...

Page 10: ...few seconds IC E C 0 OFF and the stop time default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while DC is blinking Each pressing of the button chan...

Page 11: ...or temperature Set temperature There is a dot after the set temperature figure Set temperature does not display when the unit is in DRY operation or FAN operation Set temperature may not display depen...

Page 12: ...toward you to disengage one of the front panel shafts 2 Disengage the front panel shaft on the other side in the same manner 3 After disengaging both front panel shafts pull the front panel toward you...

Page 13: ...ters into slots of the front grille Close the front panel slowly and push the panel at the 3 points IFRONT I I Accessory filter I Filter type Ag ion filter I Micro filter PM 2 5 Maintenance The access...

Page 14: ...filter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Part No KAF970A45 KAF057A41 KAF...

Page 15: ...ctuations It automatically resumes operation in about 3 minutes Voltage range protection 160V 265V A sound is heard A sound like flowing water This sound is generated because the refrigerant in the ai...

Page 16: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflow...

Page 17: ...ker and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood...

Page 18: ...OR E1 CIRCUIT BOARD FAULT E5 OL STARTED E7 DC FAN MOTOR FAULT E8 OVERCURRENT INPUT F3 HIGH TEMPERATUREDISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING OUTDOOR HO SENSOR FAULT UNIT H6 FAULTY...

Page 19: ......

Page 20: ......

Page 21: ...installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Dra...

Page 22: ...as stopvalve sservice port thenfullyopenliquidand gas stopvalves Do not attempt to turn valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a t...

Page 23: ...ue 32 7 39 9N m 21 6 27 4N m O D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side I 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cm O D 15 9mm 61 8 75 4N m 490 61O kgf cm 10 8 14 7N m 110 150 kgf cm 6...

Page 24: ...ghtened too much it may cause condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire I...

Page 25: ...d with the unit it WARNING ____________________________________ 1 _a1J_ 1 _N_ _ 6 Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst conn...

Page 26: ...oor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L 10 Caulk thegap between the pipe and the front grillewith putty 11 After completing refrigerant piping wiring and drain p...

Page 27: ...id pipeend Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 298 X 821 X 235 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X 906 X 235 906 1...

Page 28: ...s I When there is no work space because the unit is close to ceiling CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pushing up pull...

Page 29: ...length is 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensi...

Page 30: ...the unit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGi l li11 114 The outdoor unit should be posit...

Page 31: ...nt gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leak...

Page 32: ...3P665364 12T M21P085E DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL l MODELS F GTKY50UV16V2 F GTKY50UV16U2 F GTKY50UV16V39 F GTKY50UV16U39 F GTKY50UV16V3F J C JNVERTER 3P665364 12T M21P085E...

Reviews: