Function Details
ESIE15-13B
36
Function and Control
3.2
Outdoor Unit
3.2.1 Abnormal Stop
When the following items show abnormal values, the thermostat turns OFF and error is
determined based on the number of retry in order to protect the compressor and other devices.
3.2.2 Restart Standby
To prevent compressor from frequent ON/OFF and equalize pressure in refrigerant line,
conducts forced thermostat OFF for 3 minutes after compressor stopping. Moreover, outdoor
unit fan conducts residual operation for a period of time to expedite equalization and prevent
refrigerant from entering in evaporator.
Item
Criteria
Number of retry
Low pressure
LPS activated or 0.12 MPa or less continues
for 5 minutes
6 times in 200 minutes
High pressure
HPS activated or
over 3.92 MPa continues for 1 minute
15 times in 300 minutes
Discharge pipe
temperature
RZQG71L
Temperature over 110°C continues for 15
minutes or temperature exceeds 125°C
10 times in 200 minutes
RZQG100-140L
Temperature over 110°C continues for 10
minutes or temperature exceeds 120°C
Power supply
Negative-phase-sequence power
None (No retry)
RZQG71L
RZQG100-140L
Cooling
Heating
A
480
480
200
B
480
480
200
C
480
480
200
D
480
480
200
E
480
480
200
F
60
10
10
G
60
30
30
H
30
30
30
I
30
30
30
OFF
OFF
ON
ON
B
A
C
D
E
0
Moves to "Stop" or "Starting control"
after completion of "Restart standby".
Restart standby complete
Thermostat OFF
Compressor
Operation
complete
Outdoor unit fan
For 3 min.
F sec.
Electronic
expansion valve
Residual
operation
G
H
sec. sec.
sec.
I
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...