Troubleshooting by Remote Controller
ESIE15-13B
178
Service Diagnosis
4.37 Field Setting Switch Abnormality
Remote
Controller
Display
UA
Applicable
Models
All models of indoor unit
Method of Error
Detection
Error Decision
Conditions
Incorrect combination indoor unit and outdoor unit
Improper field setting
Supposed
Causes
Defective indoor unit PCB and wrong wiring
Defective power supply PCB connection
Indoor-outdoor, indoor-indoor unit transmission wiring
Defective remote controller wiring
Defective indoor unit PCB
Failure for setting the number of simultaneous multi-units
Wrong wiring of crossing transition wire
Defective multi remote controller connection
Faulty connection of optional equipment