Symptom-based Troubleshooting
ESIE15-13B
100
Service Diagnosis
2.2
Equipment does not Operate
Applicable Model
All models of SkyAir series
Supposed
Causes
Fuse blown or disorder of contact in operation circuit
Defective operation switch or contact point
Defective high pressure switch
Defective magnetic switch for fan motor
Activation or fault of overcurrent relay for fan motor
Defective overcurrent relay for compressor
Defective compressor protection thermostat
Insufficient insulation in electric system
Defective contact point of magnetic switch for compressor
Defective compressor
Defective remote controller or low batteries (wireless)
Incorrect address setting of wireless remote controller
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...