technical data

600x600 4-Way Blow Ceiling Mounted Cassette 

FXZQ-M8V1B

air conditioning systems

Summary of Contents for FXZQ-M8V1B

Page 1: ...technical data 600x600 4 Way Blow Ceiling Mounted Cassette FXZQ M8V1B air conditioning systems ...

Page 2: ...ectrical Specifications 4 3 Safety device settings 5 4 Options 6 5 Control systems 7 6 Capacity tables 8 Cooling capacity tables 8 Heating capacity tables 9 7 Dimensional drawing centre of gravity 10 Dimensional drawing 10 Centre of gravity 11 8 Piping diagram 12 9 Wiring diagram 13 Wiring diagram 13 10 Sound data 14 Sound level data 14 Sound pressure spectrum 15 11 Air flow pattern 16 ...

Page 3: ... draught characteristics Vertical auto swing function moves the discharge flaps up and down for efficient air distribution throughout the room Since the flaps can move to a 0 degree position virtually no draught can be experienced 5 different air flow patterns Any one of 5 air flow patterns can be freely selected between zero and 40 degrees and will then be maintained during the operational cycle ...

Page 4: ...QTS32C15M Output high W 55 55 55 55 55 Drive Direct drive Refrigerant Name R 410A Sound Level Cooling Sound power nominal dBA 47 0 47 0 49 0 53 0 58 0 Cooling Sound Pressure High dBA 30 0 30 0 32 0 36 0 41 0 Low dBA 25 0 25 0 26 0 28 0 33 0 Piping connections Liquid OD Type Flare connection Diameter mm 6 4 6 4 6 4 6 4 6 4 Gas Type Flare connection Diameter mm 12 7 12 7 12 7 12 7 12 7 Drain Diamete...

Page 5: ...MCA A 0 80 0 80 0 80 0 80 0 90 Maximum fuse amps MFA A 15 00 15 00 15 00 15 00 15 00 Full load amps FLA A 0 60 0 60 0 60 0 60 0 70 Voltage range Minimum V 10 Maximum V 10 Notes Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits Maximum allowable voltage range variation between phases is 2 MCA MFA MCA 1 2...

Page 6: ...nits 5 Indoor Units 600X600 4 WAY BLOW CEILING MOUNTED CASSETTE FXZQ M8V1B 3 Safety device settings 3D006691K FXZQ20M8 FXZQ25M8 FXZQ32M8 FXZQ40M8 FXZQ50M8 PC BOARD FUSE 250V 5A FAN MOTOR THERMAL PROTECTOR C OFF 130 5 ON 80 20 ...

Page 7: ...tems Indoor Units 6 4 Options 3D068933 FXZQ20M8 FXZQ25M8 FXZQ32M8 FXZQ40M8 FXZQ50M8 DECORATION PANEL BYFQ60B7W1 SEALING MEMBER OF AIR DISCHARGE OUTLET KDBHQ44B60 PANEL SPACER KDBQ44B60 REPLACEMENT LONG LIFE FILTER KAFQ441B60 FRESH AIR INTAKE KIT DIRECT INSTALLATION TYPE KDDQ44X60 ...

Page 8: ...CENTRALISED REMOTE CONTROL DCS302C51 UNIFIED ON OFF CONTROL DCS301B51 SCHEDULE TIMER DST301B61 FXZQ20M8 FXZQ25M8 FXZQ32M8 FXZQ40M8 FXZQ50M8 WIRING ADAPTER KRP1B57 WIRING ADAPTER FOR ELECTRICAL APPENDICES 1 KRP2A52 WIRING ADAPTER FOR ELECTRICAL APPENDICES 2 KRP4A53 REMOTE SENSOR KRCS01 1 INSTALLATION BOX FOR ADAPTER PCB 2 KRP1B101 ELECTRICAL BOX WITH EARTH TERMINAL 3 BLOCKS KJB311A ELECTRICAL BOX W...

Page 9: ...2 5 4 6 2 5 16 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 3 2 5 4 6 2 5 18 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 3 2 5 4 5 2 5 20 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 3 2 5 4 4 2 4 21 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 3 2 5 4 4 2 4 23 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 2 2 5 4 3 2 4 25 0 2 4 1 9 2 9 2 1 3 4 2 4 3 6 2 4 3 8 2 4 4 2 2 5 4 3 2 4 27 0 2 4 1 9 2 9 2 1 3...

Page 10: ...2 4 2 4 16 7 17 0 2 6 2 6 2 6 2 6 2 6 2 5 14 7 15 0 2 7 2 7 2 7 2 7 2 7 2 7 12 6 13 0 2 9 2 8 2 8 2 8 2 8 2 8 10 5 11 0 3 0 3 0 3 0 3 0 3 0 3 0 9 5 10 0 3 1 3 1 3 1 3 1 3 0 3 0 8 5 9 1 3 1 3 1 3 1 3 1 3 1 3 1 7 0 7 6 3 2 3 2 3 2 3 2 3 2 3 2 5 0 5 6 3 4 3 4 3 4 3 4 3 4 3 4 3 0 3 7 3 5 3 5 3 5 3 5 3 5 3 5 0 0 0 7 3 7 3 7 3 7 3 7 3 7 3 5 3 0 2 2 3 9 3 9 3 9 3 9 3 7 3 5 5 0 4 1 4 1 4 1 4 0 3 9 3 7 3 5...

Page 11: ...rol this position will be a signal receiver Refer to the drawing of the infrared remote control for more details 3 When the temperature and humidity in the ceiling exceed 30 C and RH is 80 or the fresh air is inducted into the ceiling or the unit continues 24 hour operation an additional insulation is required thickness 10mm or more or glass wool or polyethylene foam 4 Though the installation is a...

Page 12: ...7 VRV Systems Indoor Units 11 Indoor Units 600X600 4 WAY BLOW CEILING MOUNTED CASSETTE FXZQ M8V1B 7 Dimensional drawing centre of gravity 7 2 Centre of gravity FXZQ M8 4D040158 ...

Page 13: ...TED CASSETTE FXZQ M8V1B 8 VRV Systems Indoor Units 12 8 Piping diagram FXZQ M8 4D040157 Filter Filter Th3 Th2 Th1 Electronic expansion valve Fan Heat exchanger Liquid pipe connection port Gas pipe connection port Flare connection Flare connection ...

Page 14: ... board Y1E Electronic expansion valve Main C1 Capacitor M1F Wired remote control F1U Fuse 훾 5A 250V R1T Thermistor air HAP Light emitting diode Service monitor green SS1 Selector switch Main sub KPR Magnetic relay M1P Infrared remote control Receiver display unit M1F Motor Indoor fan ASP Printed circuit board M1P Motor Drain pump A4P Printed circuit board M1S Motor Swing flap BS1 Push button On of...

Page 15: ...operation and ambient conditions 3 Operating conditions Power source 230V 50 Hz Cooling Indoor air temperature 27 CDB 19 CWB Outdoor air temperature 35 CDB 24 CWB Heating Indoor air temperature 20 CDB 15 CWB Outdoor air temperature 7 CDB 6 CWB Model Sound pressure level Sound power level H L Measuring location FXZQ20M8 30 25 47 FXZQ25M8 30 25 47 FXZQ32M8 32 26 49 FXZQ40M8 36 28 53 FXZQ50M8 41 33 5...

Page 16: ...evel dB 0dB 0 002µbar FXZQ32M8 4D040285A Octave band center frequency Hz Approximate treshold hearing for continuous noise Hi Low Octave band pressure level dB 0dB 0 002µbar FXZQ40M8 4D040286A Octave band center frequency Hz Approximate treshold hearing for continuous noise Hi Low Octave band pressure level dB 0dB 0 002µbar FXZQ50M8 4D040287A Octave band center frequency Hz Approximate treshold he...

Page 17: ...8A 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 1 5 m s 1 0 m s 0 5 m s 2 7 m 1 m 2 m 3 m 4 m 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 20 C 22 C 24 C 26 C 2 7 m 1 m 2 m 3 m 4 m FXZQ32M8 Cooling air velocity distribution 4 way discharge air flow direction horizontal Cooling air temperature distribution 4 way discharge air flow direction horizontal 4D040188 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 1 5 m s 1 0 m s ...

Page 18: ... 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 1 5 m s 1 0 m s 0 5 m s 2 7 m 1 m 2 m 3 m 4 m 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 20 C 22 C 24 C 26 C 2 7 m 1 m 2 m 3 m 4 m FXZQ50M8 Cooling air velocity distribution 4 way discharge air flow direction horizontal Cooling air temperature distribution 4 way discharge air flow direction horizontal 4D040190 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 1 5 m s 1 0 m s 0 ...

Page 19: ...m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 1 5 m s 1 0 m s 0 5 m s 2 7 m 1 m 2 m 3 m 4 m 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 30 C 28 C 24 C 26 C 22 C 2 7 m 1 m 2 m 3 m 4 m FXZQ32M8 Heating air velocity distribution 4 way discharge air flow direction down Heating air temperature distribution 4 way discharge air flow direction down 4D040191 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 2 5 m s 1 5 m s 1 0 m s 0 5 m s ...

Page 20: ...1 m 0 m 0 m 1 m 2 m 2 0 m s 2 5 m s 1 5 m s 1 0 m s 0 5 m s 2 7 m 1 m 2 m 3 m 4 m 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 30 C 28 C 24 C 26 C 22 C 2 7 m 1 m 2 m 3 m 4 m FXZQ50M8 Heating air velocity distribution 4 way discharge air flow direction down Heating air temperature distribution 4 way discharge air flow direction down 4D040193 4 m 3 m 2 m 1 m 0 m 0 m 1 m 2 m 2 0 m s 2 5 m s 1 5 m s 1 0 m s 0 5 m ...

Page 21: ... Indoor Units 600X600 4 WAY BLOW CEILING MOUNTED CASSETTE FXZQ M8V1B 11 VRV Systems Indoor Units 20 11 Air flow pattern ...

Page 22: ...lgium www daikineurope com EEDE06 2 03 2006 Prepared in Belgium by Lannoo Daikin equipment is designed for comfort applications For use in other applications please contact your local Daikin representative The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this publication to t...