Outline of Control (Outdoor Unit)
SiE 00-07
66
Function R-407C PLUS Series
3.17
Heating Pump-Down Residual Operation
Conduct an operation during stop mode to discharge refrigerant from the low pressure side, since liquid
refrigerant remaining in the accumulator can be sucked into the compressor during startup and dilutes the
refrigerating machine oil in the compressor and lowers the lubricating performance.
[Residual operation starting condition]
DSHi : INV discharge pipe superheat degree
Th6-Te : Suction pipe temp. -Low pressure equivalent saturation temp.
[Description of movement]
∗
Receiver gas relief solenoid valve is open and liquid refrigerant is moved to liquid line for 60 seconds
after entering pump-down residual operation.
However, this relief solenoid valve closes at Th6-Te < 0.
[Ending condition]
&
Thermostat ON
→
OFF
OR
DSHi < 20˚C
Th6 – Te < 10˚C
Outdoor unit
Indoor unit
Compressor
Motorized valve
Solenoid valve for hot gas
Motorized valve
Movement
67Hz+OFF
Initial 2000 pls
→
PI control when SHS = 10˚C
ON (equalization)
500 pls (all indoor unit)
&
DSHi > 90˚C
Th6 – Te < 10˚C
LP < 0.07MPa
Tc > 48.6˚C
10 min elapse
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...