Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
51
3.6
Demand Control
Forcibly reduces the outdoor unit capacity based on an external contact input (demand input) to decrease
power consumption. The following three types of demand control are provided.
Other protection control functions have precedence over the above operations.
∗
Optional PCB is required for this control. (DTA104A61, 62)
Compressor upper-limit frequency Capacity reduction guideline
Demand control 1
A
Reduces power consumption to approx. 70%
Demand control 2
B
Reduces power consumption to approx. 40%
Demand control 3
All compressors in stop mode
Forced thermostat OFF
Model
Upper-limit frequency (A)
Model
Upper-limit frequency(B)
INV
STD1
STD2
INV
STD1
STD2
RSXYP16KJ
46Hz
+ON
—
RSXYP16KJ
52Hz
+OFF
—
RSXYP18KJ
52Hz
+ON
—
RSXYP18KJ
62Hz
+OFF
—
RSXYP20KJ
52Hz
+ON
—
RSXYP20KJ
62Hz
+OFF
—
RSXYP24KJ
71Hz
+ON
+OFF
RSXYP24KJ
75Hz
+OFF
+OFF
RSXYP26KJ
71Hz
+ON
+OFF
RSXYP26KJ
75Hz
+OFF
+OFF
RSXYP28KJ
71Hz
+ON
+OFF
RSXYP28KJ
75Hz
+OFF
+OFF
RSXYP30KJ
71Hz
+ON
+OFF
RSXYP30KJ
75Hz
+OFF
+OFF
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...