SiE 00-07
Product Outline
General Information R-407C PLUS Series
5
1.3
Model Configuration and Combination
Number of units and capacity of connectable indoor units
Connectable indoor unit
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the total
capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the rated capacity
of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor units. Select
models so the total capacity of connected indoor units conforms to the specification.
Combination
example
RSXYP20KJ / 20-unit system
Indoor unit / FXYCP25K
×
20 units
Standard
series
Equivalent output
16HP
18HP
20HP
24HP
R-407C VRV PLUS series system model
RSXYP16KJ
RSXYP18KJ
RSXYP20KJ
RSXYP24KJ
Outdoor unit combination
Main unit
RXYP8KJ
RXYP10KJ
RXYP10KJ
RXYP16KJ
Sub unit
RXEP8KJ
RXEP8KJ
RXEP10KJ
RXEP8KJ
Total number of connectable indoor units
Up to 20 units
Up to 32 units
Total capacity of connectable indoor units
200~520
225~585
250~650
300~780
Standard
series
Equivalent output
26HP
28HP
30HP
R-407C VRV PLUS series system model
RSXYP26KJ
RSXYP28KJ
RSXYP30KJ
Outdoor unit combination
Main unit
RXYP16KJ
RXYP20KJ
RXYP20KJ
Sub unit
RXEP10KJ
RXEP8KJ
RXEP10KJ
Total number of connectable indoor units
Up to 32 units
Total capacity of connectable indoor units
325~845
350~910
375~975
Indoor unit
Model name
Ceiling
mounted
cassette type
Multi-flow type
FXYFP32KVE·40KVE·50KVE·63KVE·80KVE·100KVE·125KVE
Double flow type
FXYCP20KV1·25KV1·32KV1·40KV1·50KV1·63KV1·80KV1·125KV1
Corner type
FXYKP25KV1·32KV1·40KV1·63KV1
Ceiling mounted built-in type
FXYSP20KV1·25KV1·32KV1·40KV1·50KV1·63KV1·80KV1·100KV1·125KV1
Ceiling mounted duct type
FXYMP40KV1·50KV1·63KV1·80KV1·100KV1·125KV1·200KV1·250KV1
Ceiling suspended type
FXYHP32KV1·63KV1·100KV1
Wall mounted type
FXYAP20KV1·25KV1·32KV1·40KV1·50KV1·63KV1
Floor standing type
FXYLP20KV1·25KV1·32KV1·40KV1·50KV1·63KV1
Concealed floor standing type
FXYLMP20KV1·25KV1·32KV1·40KV1·50KV1·63KV1
New refrigerant model code
P20
type
P25
type
P32
type
P40
type
P50
type
P63
type
P80
type
P100
type
P125
type
P200
type
P250
type
Selecting model capacity
2.2kW
2.8kW
3.5kW
4.5kW
5.6kW
7.0kW
9.0kW
11.2kW 14.0kW 22.4kW 28.0kW
Equivalent output
0.8HP
1HP
1.25HP
1.6HP
2.0HP
2.5HP
3.2HP
4HP
5HP
8HP
10HP
(V0806)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...