Troubleshooting by Remote Controller
SiE 00-07
118
Troubleshooting R-407C PLUS Series
2.3
Self-diagnosis by Wireless Remote Controller
In Case of BRC7A~
Type
If operation stops due to malfunction, the light reception section operation LED blinks. The malfunction
code can be decided by the following procedure. (If operation stops due to malfunction, you can find out
the cause by checking the malfunction code, or you can find out what the most recent malfunction code is
during normal operation.)
1. Push INSPECTION/TEST, and select “inspection.”
Operation then enters the inspection mode. “UNIT” lights and unit No. display “0” blinks.
2. Unit No. setting
Change the unit No. by pushing the “advance” or “backward” button, and continue pushing until the
buzzer (*1) sounds from the indoor unit.
*1 Buzzer sound times
3 times :
Carry out all of the following operations.
1 time :
Carry out operations 3 and 4. Carry out operation 4 until the buzzer sounds continuously.
When the buzzer sounds continuously. The malfunction code is set.
Continuous :
There is no malfunction.
The upper digit of the code changes as shown below by pushing the “advance” or “backward” button.
3. Push the operation mode selector button. The “0” (upper digit) on the left side of the malfunction code
blinks.
4. Malfunction code upper digit diagnosis Push the “advance” or “backward” button until the malfunction
code matching buzzer (*2) sounds and select the malfunction code upper digit.
*2 Buzzer sound times
Continuous :
Both upper and lower digit agree. (Malfunction code set)
2 times :
Upper digit agrees
1 time :
Lower digit agrees
5. Push the operation mode selector button.
The “0” (upper digit) on the right side of the malfunction code blinks.
6. Malfunction code lower digit diagnosis Push the “advance” or “backward” button until the malfunction
code matching buzzer sounds continuously, and select the malfunction code lower digit.
The lower digit of the code changes as shown below by pushing the “advance” or “backward” button.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...