10
|
Maintenance and service
Installer and user reference guide
35
FXUA50~100AVEB
VRV system air conditioner
4P673843-1 – 2022.01
10.5 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the
atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Please contact your installer for more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
▪
Do NOT pierce or burn refrigerant cycle parts.
▪
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
▪
Be aware that the refrigerant inside the system is odourless.
WARNING
▪
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
▪
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
▪
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
10.5.1 About the refrigerant leakage sensor
WARNING
The R32 refrigerant leakage sensor must be replaced after every detection or at the
end of its lifetime. ONLY authorised persons may replace the sensor.
NOTICE
Functionality of the safety measures are periodically automatically checked. In case
of malfunction, an error code will be displayed on the user interface.