5
|
About the system
Installer and user reference guide
24
FXUA50~100AVEB
VRV system air conditioner
4P673843-1 – 2022.01
d
Suction air
e
Discharge air
f
Refrigerant transmission cable
g
Drain pipe
h
Suction grille and air filter
5.2 Information requirements for fan coil units
Item
Symbol
Value
Unit
Cooling capacity (sensible)
P
rated,c
A
kW
Cooling capacity (latent)
P
rated,c
B
kW
Heating capacity
P
rated,h
C
kW
Total electric power input
P
elec
D
kW
Sound power level (cooling)
L
WA
E
dB(A)
Sound power level (heating)
L
WA
F
dB(A)
Contact details:
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň
Skvrňany, Czech Republic
A
B
C
D
E
F
FXUA 50
3.8
1.8
6.3
0.029
55
55
FXUA 71
5.5
2.5
9
0.055
58
58
FXUA100
8.1
3.1
12.5
0.117
65
65