FXFSQ-AVM EDFMT391769A
25
8.3 Cooling Capacity for Te: 9°C
For
VRV
indoor units only at Te: 9°C / mixed combination of
VRV
and residential indoor units
Model
Capacity
indication
Indoor air temp.
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
FXFSQ25AVM
25
1.4
1.4
1.8
1.8
2.1
2.1
2.3
2.3
2.4
2.4
2.5
2.3
2.7
2.2
FXFSQ32AVM
32
1.8
1.8
2.2
2.2
2.8
2.8
3.0
2.9
3.1
2.8
3.2
2.7
3.4
2.6
FXFSQ40AVM
40
2.3
2.3
2.8
2.8
3.5
3.5
3.8
3.7
3.9
3.7
4.1
3.6
4.3
3.4
FXFSQ50AVM
50
2.5
2.5
3.3
3.3
4.1
4.1
4.5
4.4
4.7
4.3
5.0
4.0
5.2
3.7
FXFSQ63AVM
63
3.3
3.3
4.2
4.2
5.2
5.1
5.8
5.3
5.9
5.2
6.3
5.0
6.6
4.7
FXFSQ80AVM
80
4.3
4.3
5.3
5.2
6.7
6.0
7.3
6.2
7.5
6.1
8.0
5.9
8.4
5.7
FXFSQ100AVM
100
5.2
5.2
6.4
6.4
8.2
7.6
8.9
7.8
9.2
7.6
9.7
7.5
10.3
7.4
FXFSQ125AVM
125
6.4
6.2
8.3
7.6
10.4
8.8
11.3
9.0
11.7
9.0
12.3
8.7
13.0
8.7
FXFSQ140AVM
140
7.4
7.1
9.6
8.6
11.9
10.0
13.0
10.2
13.5
10.2
14.3
10.0
15.0
9.7
TC: Total capacity: kW
SHC: Sensible heat capacity: kW
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
8.4 Heating Capacity
Model
Capacity
indication
Indoor air temp.
16°CDB
18°CDB
20°CDB
21°CDB
22°CDB
24°CDB
kW
kW
kW
kW
kW
kW
FXFSQ25AVM
25
3.4
3.2
3.2
3.1
3.0
2.8
FXFSQ32AVM
32
4.2
4.2
4.0
3.9
3.7
3.5
FXFSQ40AVM
40
5.2
5.2
5.0
4.8
4.7
4.4
FXFSQ50AVM
50
6.6
6.6
6.3
6.1
5.9
5.5
FXFSQ63AVM
63
8.4
8.4
8.0
7.7
7.5
7.0
FXFSQ80AVM
80
10.5
10.5
10.0
9.7
9.4
8.7
FXFSQ100AVM
100
13.1
13.1
12.5
12.1
11.7
10.9
FXFSQ125AVM
125
16.8
16.8
16.0
15.5
15.0
13.9
FXFSQ140AVM
140
18.9
18.9
18.0
17.4
16.8
15.7
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
Summary of Contents for FXFSQ-AVM
Page 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Page 2: ......
Page 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Page 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Page 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Page 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Page 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Page 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Page 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Page 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Page 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Page 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Page 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Page 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Page 55: ......