12 Operation

Installation and operation manual

20

FWF02~05D

Fan coil units

3P443944-9T – 2023.01

This operation manual offers a non-exhaustive overview of the main
functions of the system.

For  more  information  about  the  user  interface,  see  the  operation
manual of the installed user interface.

12

Operation

12.1

Operation range

NOTICE

When  unit  starts  to  operate,  it  runs  at  a  low  speed  for  a
certain  period  before  it  reaches  set  point.  This  is  not  a
malfunction.

The  following  conditions  are  standard  operating  limits.  For  different
conditions, please consult the dealer.

Mode

Condition Air

temperature
limit, (DB/WB)

Water
temperature
limit, (in/out)

Water
delta T,
ΔT

Cooling
(˚C)

Min.

15/12.5

5/8

3 to 10

Max.

33/26

18/28

Heating
(˚C)

Min.

18/15

45/40

5 to 20

Max.

25/15

80/75

13

Energy saving and optimum
operation

Observe  the  following  precautions  to  ensure  the  system  operates
properly.

▪ Adjust  the  air  outlet  properly  and  avoid  direct  air  flow  to  room

inhabitants.

▪ Adjust  the  room  temperature  properly  for  a  comfortable

environment. Avoid excessive heating or cooling.

▪ Prevent  direct  sunlight  from  entering  a  room  during  cooling

operation by using curtains or blinds.

▪ Ventilate  often.  Extended  use  requires  special  attention  to

ventilation.

▪ Keep doors and windows closed. If the doors and windows remain

open,  air  will  flow  out  of  your  room  causing  a  decrease  in  the
cooling or heating effect.

▪ Be  careful  NOT  to  cool  or  heat  too  much.  To  save  energy,  keep

the temperature setting at a moderate level.

▪ NEVER place objects near the air inlet or the air outlet of the unit.

Doing  so  may  cause  a  reduced  heating/cooling  effect  or  stop
operation.

▪ Condensation  may  form  if  the  humidity  is  above  80%  or  if  the

drain outlet gets blocked.

NOTICE

Do  NOT  use  the  system  for  other  purposes.  In  order  to
avoid  any  quality  deterioration,  do  NOT  use  the  unit  for
cooling  precision  instruments,  food,  plants,  animals,  or
works of art.

CAUTION

Do  NOT  operate  the  system  when  using  a  room
fumigation-type  insecticide.  Chemicals  could  collect  in  the
unit,  and  endanger  the  health  of  people  who  are
hypersensitive to chemicals.

14

Maintenance and service

14.1

Maintenance safety precautions

DANGER: RISK OF BURNING/SCALDING

DANGER: RISK OF ELECTROCUTION

NOTICE

Keep  the  air  filter  clean  and  check  the  airflow  rate
periodically.

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel.

▪ Make sure you do NOT touch a conductive section.

▪ Do  NOT  rinse  the  outside  of  the  unit.  This  may  cause

electric shocks or fire.

To clean the outside of your fan coil unit:

1

Switch off the fan coil unit.

2

Clean the outside of the fan coil unit with a soft cloth.

CAUTION

▪ Do NOT obstruct the air outlet or inlet of the unit in any

way.

▪ Do  NOT  place  damp  or  wet  clothing  on  the  air  outlet

grille of the unit.

▪ Do NOT pour liquids inside the equipment.

Never clean your fan coil unit with:

▪ any aggressive chemical solvent,

▪ water hotter than 50°C.

For  maintenance  of  your  fan  coil  unit,  contact  your  installer  or
service company.

14.2

Precautions for maintenance and
service

NOTICE

NEVER  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work. However, as
end  user,  you  may  clean  the  air  filter,  suction  grille,  air
outlet and outside panels.

WARNING

NEVER  replace  a  fuse  with  a  fuse  of  a  wrong  ampere
ratings  or  other  wires  when  a  fuse  blows  out.  Use  of  wire
or copper wire may cause the unit to break down or cause
a fire.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

NOTICE

Do  NOT  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

Summary of Contents for FWF02D

Page 1: ...Installation and operation manual Fan coil units English Installation and operation manual Fan coil units FWF02D FWF03D FWF04D FWF05D...

Page 2: ...kad gaminiai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami...

Page 3: ...ed in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Com...

Page 4: ...rille 21 14 4 After a long stop period 22 14 5 Before a long stop period 22 14 6 After sales service and warranty 22 14 6 1 Recommended maintenance and inspection 22 14 6 2 Shortened maintenance and r...

Page 5: ...the terminals see the warning label for persons performing service and maintenance CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit WARNING This...

Page 6: ...the claims agent of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport Prepare in advance the path along which you want to bri...

Page 7: ...e sure the installation site withstands the weight and vibration of the unit Take care that in the event of a water leak water cannot cause any damage to the installation space and surroundings Choose...

Page 8: ...per part of the packing a to create ceiling opening according to the outlines specified on the paper pattern Attach paper pattern to the unit using the four screws d from the accessory set and create...

Page 9: ...ation Type a mm Standard Model BYFQ60B Design Panel BYFQ60C No valve 600 660 595 600 Factory mounted valve 652 660 652 A a a A Hang the unit from the suspension bolts then adjust the size of the openi...

Page 10: ...er keeps circulating in the unit condensation will form on the unit and water may drip NOTICE Make sure to insulate all piping Any exposed piping might cause condensation DANGER RISK OF BURNING SCALDI...

Page 11: ...wn 1 1 5 m a a Hanging bar Allowed Not allowed Condensation Take measures against condensation Insulate the complete drain piping in the building Combining drain pipes You can combine drain pipes Make...

Page 12: ...panel Make sure there is no gap between the unit body and the decoration panel Possible consequence Air might leak and cause dew drop Make sure no oil remains on the plastic parts of the decoration p...

Page 13: ...NOTICE The PCB connection of the valves is only required when the Daikin ON OFF valve kit EKWV2V3W5A EKWV3V3W5A is used Technical specifications of the valves Kvs value Max operation pressure PN bar...

Page 14: ...1 3 way on off valve kit d 3 Valve insulations e and tie wraps m 2 way on off valve kit e m 3 way on off valve kit e m 4 The actuator surface f and the end of cable g are colour coded to prevent switc...

Page 15: ...ore the earth wire is in case the power supply is pulled loose from the stress relief WARNING After finishing the electrical work confirm that each electrical component and terminal inside the electri...

Page 16: ...er supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III NOTICE Precautions...

Page 17: ...part of the X1M terminal 6 Cable clamps c c 7 7 Configuration 7 1 Decorative panel setting Make the following field settings so that they correspond with the actual installation setup and with the nee...

Page 18: ...2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G 1 2 W O N 1 G a b c d 1 2 W O N 1 G 35 a b c d 36 45 53 8 Commissioning NOTICE Do NOT interrupt the test run 8 1 Checklist before commissioning 1 After the ins...

Page 19: ...the unit be sure the installation has been carried out correctly by an installer WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continu...

Page 20: ...ng precision instruments food plants animals or works of art CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 21: ...with a soft cloth If it is difficult to remove stains use water or a neutral detergent 14 3 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6 months If the air in the...

Page 22: ...rder to keep your unit in operation as long as possible Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the unit The manufa...

Page 23: ...your installer and state the symptoms the complete model name of the unit with manufacturing number if possible and the installation date 15 1 Relocation Contact your dealer to remove and reinstall th...

Page 24: ...2 A1P C305 1 3 BLK X36A YLW BRN 1 5 MSW M1S BLK BLK BRN BLU X2M HEAT COOL BLU RED BRN BLU ORG RED 1 3 X35A 1 3 1 5 1 1 1 8 7 1 4 3 A3P H3P X4A X2A X4A 06 01 A2P X1A C1 N X3A H1P H2P L A1 CA F1U Z2C GR...

Page 25: ...X20A BLDC motor X24A Fan modulation X25A Drain pump X27A Power supply X32A Cooling valve X33A R C signal and valve X35A Electrical heater X36A Stepping motor Decoration panel X37A Heating valve X50A...

Page 26: ...ata Installation and operation manual 26 FWF02 05D Fan coil units 3P443944 9T 2023 01 62 5 82 R 1 3 92 65 5 25 50 77 641 5 29 138 700 50 77 45 68 25 22 Side views with design panel mm 620 308 5 49 55...

Page 27: ...t grejanja Total electric power input Elektrische Gesamtleistungsaufnahme Entr e lectrique totale Totaal opgenomen vermogen Potencia el ctrica de entrada total Potenza elettrica totale assorbita Entra...

Page 28: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P443944 9T 2023 01 Copyright 20...

Reviews: