Troubleshooting
SiBE01-829
50
Service Diagnosis
4.6
High
Pressure Control in Cooling
or
Outdoor Heat
Exchanger Thermistor Abnormality
Remote
Controller
Display
F6
Method of
Malfunction
Detection
High-pressure control (stop) is activated in the cooling mode if the temperature being sensed by
the heat exchanger thermistor exceeds the limit.
The temperature detected by the outdoor heat exchanger thermistor is used to determine the
abnormal thermistor.
Malfunction
Decision
Conditions
Activated when the temperature being sensed by the heat exchanger thermistor rises above
68°C.
Deactivated when the temperature drops below 50°C.
When the outdoor heat exchanger thermistor input is 5 V or more during compressor
operation.
Supposed
Causes
The installation space is not large enough.
Faulty outdoor unit fan
Faulty outdoor heat exchanger thermistor
Stop valve closed
Dirty heat exchanger
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...