SiBE01-829
Troubleshooting
Service Diagnosis
49
4.5.2
Room Temperature Thermistor
Remote
Controller
Display
C9
Method of
Malfunction
Detection
The temperatures detected by the room temperature thermistor is used to determine thermistor
error.
Malfunction
Decision
Conditions
When the room temperature thermistor input is more than 5 V, or 0 V during compressor
operation
∗
.
∗
(Reference)
Room temperature thermistor: 30
Ω
or less, or 490k
Ω
or more.
Supposed
Causes
Faulty thermistor
Faulty PCB
Troubleshooting
Check No.06
Refer to P.55
Caution
Be sure to turn off power switch before check the resistance value, or
parts damage may be occurred.
(R8505)
Check No. 06
Check the thermistor resistance
value.
YES
NO
Replace the thermistor.
(Replace the display PCB.)
Replace the indoor unit PCB.
Is it normal?
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...