background image

MODELS

FTXZ25NV1B
FTXZ35NV1B
FTXZ50NV1B

RXZ25NV1B
RXZ35NV1B
RXZ50NV1B

INSTALLATION

MANUAL

R32 Split Series

English

Français

Español

Italiano

Ελληνικά

Pyccкий

Türkçe

Installation manual

R32 Split series

Manuel d’installation

Série split R32

Manual de instalación

Serie Split R32

Manuale d’installazione

Serie Multiambienti R32

Εγχειρίδιο εγκατάστασης

διαιρούμενης σειράς R32

Руководство по монтажу

Серия R32 с раздельной установкой

Montaj kılavuzları

R32 Split serisi

00_CV_3P338604-1C.indd   1

9/10/2013   1:30:11 PM

Summary of Contents for FTXZ25NV1B

Page 1: ...ий Türkçe Installation manual R32 Split series Manuel d installation Série split R32 Manual de instalación Serie Split R32 Manuale d installazione Serie Multiambienti R32 Εγχειρίδιο εγκατάστασης διαιρούμενης σειράς R32 Руководство по монтажу Серия R32 с раздельной установкой Montaj kılavuzları R32 Split serisi 00_CV_3P338604 1C indd 1 9 10 2013 1 30 11 PM ...

Page 2: ...ge 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 20G FTXZ25NV1B FTXZ35NV1B FTXZ50NV1B RXZ25NV1B RXZ35NV1B RXZ50NV1B Shinri Sada Manager Quality Control Department DAIKIN TCF 032 04 2013 DEKRA Certification B V NB0344 2159619 0551 EMC 3SB65451 20G fm Page 1 Tuesday July 2 2013 10 49 AM ...

Page 3: ...or Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evacuating the air with a vacuum pump and checking gas leakage 14 7 Wiring 15 8 Connecting the humidifying hose 16 9 Setting the humidifying hose length 16 Installation Tips 17 Removing and installing the front panel 17 Removing and i...

Page 4: ...nly Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire Use a cable of suitable length Do not use tapped wires or an extension lead as this may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of ...

Page 5: ...ing the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to the specified method such as with a torque wrench If the flare nut is too tight it may crack after prolonged use causing refrigerant leakage Take adequ...

Page 6: ...et are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shorten indoor unit life 6 cool warm air is circulated throughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 th...

Page 7: ... and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side m...

Page 8: ...not install the trap to the G humidifying hose as much as possible The flare connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidifying hose more than 90 Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line CAUTION Set the piping length from 1 5m to 10m 250mm fro...

Page 9: ...al board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hole of 65mm in the wall so it has a down slope toward the outside 2 Insert a wall embedded pipe into the hole 3 Insert a wall hole cover into wall ...

Page 10: ...mm from the joint or an elbow field supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose Replacing onto the left side 1 Remove the insulation fixing screw on the right to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove ...

Page 11: ... bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G Humidifying hose Refrigerant pipe 1 Replace the drain plug and drain hose Refer to 4 3 How to replace the drain plug and drain hose on page 8 2 Pull in the refrigerant pipes and lay them so that it matches the liquid and...

Page 12: ... the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid fits securely then close the service lid 1 2 3 Terminal block Wire retainer Use the specified wire type Electrical wiring box Shape wires so that the service lid will fit securely Firmly secure wire retainer so that wires sustain no external stress 1 2 3 1 2 3 L N 1 Fir...

Page 13: ...n connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially available drain socket nominal diameter 13mm as a joint ɸ18 Commercially available drain socket nominal diameter 13mm Commercially available rigid polyvinyl chloride pipe nominal diameter 13mm Drain hose supplied with the indoor...

Page 14: ...drain socket for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of at least 30mm in height under the outdoor unit s feet 3 In cold areas do not use a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance Drain hole Air outlet side ɸ18 hole Bottom view Bottom frame H Drain socket Hose available commerc...

Page 15: ... Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a cap If no flare cap is available cover the flare mouth with tape to keep dirt or water out Rain Wall 5 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the follow...

Page 16: ...o and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg The vacuum pump should run for at least 10 minutes 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer d...

Page 17: ...ecommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05RN 1 Firmly fix the wires with the terminal screws 1 2 Inter unit wire 4 core 1 5mm or more 60245 IEC 57 H05RN Indoor unit Outdoor unit Circuit breaker 16A Earth leakage circuit breaker Power supply 50Hz 220 240V Earth Firm...

Page 18: ...onds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller toward the indoor unit The currently set humidifying hose length will be displayed No setting is made by default 4 Press and set the humidifying hose length The humidifying hose length can be set in 5 stages 3M 3 1M 4M 4 1M ...

Page 19: ...oval method 1 Remove the front panel 2 Direct the flap and the auxiliary flap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right 3 screws See Fig 2 5 While lifting up the front grille top with the flathead screwdriver unhook the tabs and remove the front grille right See Fig 3 6 Remove the screws that secure the front grille left 2 screws See Fig 4 7 ...

Page 20: ...ection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions Electrical wiring box Electrical wiring box cover Tabs HA connector S21 white How to route the HA connection cord Pump down operation In order to protect the environment be sure to pump down when relocating or disposing of ...

Page 21: ... display unit black upward and remove the air filter Display unit black Air filter 3 Install the B photocatalytic air purifying and deodorising filter B Photocatalytic air purifying and deodorising filter Tabs 4 Restore the air filter and the dust box to the original positions 3 Trial operation and testing 3 1 Measure the supply voltage and make sure that it falls in the specified range 3 2 Trial operat...

Page 22: ...ation noise narrower detectable range of the INTELLIGENT EYE sensor Are the air filter and the dust box attached properly Noise water leakage CLEANING FILTER operation disabled Did you install the photocatalytic air purifying and deodorising filter Noise water leakage CLEANING FILTER operation disabled Have you performed a leak test to ensure that there are no refrigerant gas leaks Incomplete coolin...

Page 23: ...Two dimensional bar code is a code for manufacturing 3P338604 1C M12B406B 1310 HT 00_CV_3P338604 1C indd 2 9 10 2013 1 30 12 PM ...

Reviews: