background image

Installation manual

Daikin room air conditioner

English

Installation manual

Daikin room air conditioner

FTXTM30R2V1B
FTXTM40R2V1B

Summary of Contents for FTXTM30R2V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTM30R2V1B FTXTM40R2V1B ...

Page 2: ...his appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC st...

Page 3: ... cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under ov...

Page 4: ...nd installation shall comply with the applicable legislation In Europe EN378 is the applicable standard 5 1 Preparing the installation site WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources e g open flames an operating gas appliance or an operating electric heater The room size shall be as specifie...

Page 5: ...0 Ø65 mm h Liquid pipe end Class 40 Ø80 mm i Center of the unit 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire NOTICE Be sure to seal the gaps around the pipes with sealing material field supply in order to prevent water leakage 1 Bore a 65 mm f...

Page 6: ...ulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise ...

Page 7: ... refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible 1 Connect refrigerant piping to the unit using flare connections 2 Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c In...

Page 8: ...imals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Cable clamp 5 Strip the wire ends approximately 15 mm 6 Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals 7 Connect the earth wire to the corresponding terminal 8 Fi...

Page 9: ...mp will start to blink ON OFF b a a Operation lamp b Indoor unit ON OFF switch 6 Press the indoor unit ON OFF switch while the operation lamp is blinking Address jumper Address Factory setting 1 After cutting with nippers 2 INFORMATION If the setting could NOT be completed while the operation lamp was blinking repeat the setting process from the beginning 7 When the setting is complete keep presse...

Page 10: ...est run can be disabled if necessary 2 When the test run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 10 2 1 To perform a test run using the user interface 1 Press to switch the system on 2 Press and simultaneously 3 Press select and press Result Test run operation will stop aut...

Page 11: ...se amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure senso...

Page 12: ...3P482320 13U 2021 03 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...

Reviews: