3 About the unit
Installation manual
3
FTXTA30A2V1BW
Split system air conditioner
3P482320-9M – 2019.04
▪
Spare SSID sticker.
Do NOT throw away the spare sticker. Keep
it in a safe place in case it is needed in future (e.g. in case the
front grille was replaced attach it to the new front grille).
3
About the unit
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
3.1
System layout
g
f
h
i
d
e
b
c
a
a
Front panel
b
Service cover
c
SSID sticker
d
Air filter
e
Intelligent eye sensor
f
Caulk pipe hole gap with putty
g
Refrigerant piping, drain hose and interconnection cable
h
Insulation tape
i
Titanium apatite deodorizing filter and silver particle filter
(Ag-ion filter)
3.2
About the wireless LAN adapter
For detailed specifications, installation instructions, setting methods,
FAQ, declaration of conformity and the latest version of this manual,
visit
http://www.onlinecontroller.daikineurope.com
.
INFORMATION
▪ Daikin Industries Czech Republic s.r.o. declares that
the radio equipment type inside of this unit is in
compliance with Directive 2014/53/EU.
▪ This unit is considered as combined equipment
according to the definition of Directive 2014/53/EU.
3.2.1
Precautions when using the wireless
adapter
Do NOT use near:
▪
Medical equipment.
E.g. persons using cardiac pacemakers or
defibrillators.
This
product
may
cause
electromagnetic
interference.
▪
Auto-control equipment.
E.g. automatic doors or fire alarm
equipment. This product may cause faulty behaviour of the
equipment.
▪
Microwave oven.
It may affect wireless LAN communications.
3.2.2
Basic parameters
Parameter
Value
Frequency range
2400 MHz~2483.5 MHz
Radio protocol
IEEE 802.11b/g/n
Radio frequency channel
1~11
Output power
0 dBm~18 dBm
Parameter
Value
Effective radiated power
17 dBm (11b) / 13 dBm (11g) /
12 dBm (11n)
Power supply
DC 3.3 V / 500 mA
4
Preparation
4.1
Preparing the installation site
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (e.g. open flames, an operating
gas appliance, or an operating electric heater). The room
size shall be as specified in the General safety precaution.
4.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated
properly.
▪
Wall insulation
. When conditions in the wall exceed 30°C and a
relative humidity of 80%, or when fresh air is inducted into the
wall, then additional insulation is required (minimum 10 mm
thickness, polyethylene foam).
▪
Wall strength.
Check whether the wall or the floor is strong
enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.
▪
Spacing.
Install the unit at least 1.8 m from the floor and keep the
following requirements in mind for distances from the walls and
the ceiling:
≥50
≥50
≥30
(mm)
Note:
Make sure that there are no obstacles within 500 mm under
the signal receiver. They may influence reception performance of the
user interface.
5
Installation
WARNING
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable
legislation. In Europe, EN378 is the applicable standard.
5.1
Opening the indoor unit
5.1.1
To open the front panel
1
Hold the front panel on both sides and open it.