3 About the unit

Installation manual

3

FTXTA30A2V1BW
Split system air conditioner
3P482320-9M – 2019.04

Spare SSID sticker. 

Do NOT throw away the spare sticker. Keep

it  in  a  safe  place  in  case  it  is  needed  in  future  (e.g.  in  case  the
front grille was replaced attach it to the new front grille).

3

About the unit

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

3.1

System layout

g

f

h

i

d

e

b

c

a

a

Front panel

b

Service cover

c

SSID sticker

d

Air filter

e

Intelligent eye sensor

f

Caulk pipe hole gap with putty

g

Refrigerant piping, drain hose and interconnection cable

h

Insulation tape

i

Titanium apatite deodorizing filter and silver particle filter
(Ag-ion filter)

3.2

About the wireless LAN adapter

For detailed specifications, installation instructions, setting methods,
FAQ, declaration of conformity and the latest version of this manual,
visit 

http://www.onlinecontroller.daikineurope.com

.

INFORMATION

▪ Daikin  Industries  Czech  Republic  s.r.o.  declares  that

the  radio  equipment  type  inside  of  this  unit  is  in
compliance with Directive 2014/53/EU.

▪ This  unit  is  considered  as  combined  equipment

according to the definition of Directive 2014/53/EU.

3.2.1

Precautions when using the wireless
adapter

Do NOT use near:

Medical  equipment.

  E.g.  persons  using  cardiac  pacemakers  or

defibrillators. 

This 

product 

may 

cause 

electromagnetic

interference.

Auto-control  equipment.

  E.g.  automatic  doors  or  fire  alarm

equipment.  This  product  may  cause  faulty  behaviour  of  the
equipment.

Microwave oven.

 It may affect wireless LAN communications.

3.2.2

Basic parameters

Parameter

Value

Frequency range

2400 MHz~2483.5 MHz

Radio protocol

IEEE 802.11b/g/n

Radio frequency channel

1~11

Output power

0 dBm~18 dBm

Parameter

Value

Effective radiated power

17 dBm (11b) / 13 dBm (11g) /
12 dBm (11n)

Power supply

DC 3.3 V / 500 mA

4

Preparation

4.1

Preparing the installation site

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

4.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

Air flow.

 Make sure nothing blocks the air flow.

Drainage.

  Make  sure  condensation  water  can  be  evacuated

properly.

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

Note: 

 Make sure that there are no obstacles within 500 mm under

the signal receiver. They may influence reception performance of the
user interface.

5

Installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

5.1

Opening the indoor unit

5.1.1

To open the front panel

1

Hold the front panel on both sides and open it.

Summary of Contents for FTXTA30A2V1BW

Page 1: ...Installation manual Split system air conditioner English Installation manual Split system air conditioner FTXTA30A2V1BW ...

Page 2: ...on and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply wi...

Page 3: ...ency range 2400 MHz 2483 5 MHz Radio protocol IEEE 802 11b g n Radio frequency channel 1 11 Output power 0 dBm 18 dBm Parameter Value Effective radiated power 17 dBm 11b 13 dBm 11g 12 dBm 11n Power supply DC 3 3 V 500 mA 4 Preparation 4 1 Preparing the installation site WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously opera...

Page 4: ...ide a a a Panel lock 3 Push the right arm lightly to the right to disconnect the shaft from the shaft slot on the right side a c b a Arm b Shaft c Shaft slot 4 Disconnect the front panel shaft from the shaft slot on the left side a c b a Arm b Shaft slot c Shaft 5 Remove the front panel 6 To re install the front panel perform the steps in the opposite order 5 1 4 To open the service cover 1 Remove...

Page 5: ...re clamp 5 Close the front panel Refer to 5 1 2 To close the front panel on page 4 5 1 7 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling it to the front 4 Remove the electrical wiring box cover from the 2 rear hooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re in...

Page 6: ...ial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a wall cover into the wall pipe Ø65 a b c a Wall embedded pipe b Putty c Wall hole cover 4 After completing wiring refrigerant piping and drain piping do NOT forget to seal the gap with putty 5 2 3 To re...

Page 7: ...cur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left back piping C Left bottom piping a Remove the pipe port cover here for left side piping b Remove the pipe port cover here for left bottom piping To check for water leaks 1 Remove the air filters 2 Gradually pour approximately ...

Page 8: ... may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Wire retainer 5 Stri...

Page 9: ... reference guide The indoor units are properly mounted The outdoor unit is properly mounted Air inlet outlet Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Make sure drainage flows smoothly Possible consequence Conde...

Page 10: ...OUTDOOR Outdoor unit Wire clamp Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White YLW Yellow Symbol Meaning A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heat...

Page 11: ...l strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X ...

Page 12: ...3P482320 9M 2019 04 Copyright 2019 Daikin ...