SiUS091133
Main Functions
Function and Control
34
1.6
Automatic Operation
Outline
Automatic Cooling / Heating Function
When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C, 64.4 ~ 86°F).
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value
.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating
Cooling switching point:
Tr
Tt + 3.0°C (+5.4°F) (FTXS series)
Tr
Tt + 2.5°C (+4.5°F) (FDXS series)
(2) Cooling
Heating switching point:
Tr < Tt – 2.5°C (–4.5°F)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating operation.
4. During initial operation
Tr
Ts : Cooling operation
Tr < Ts : Heating operation
FTXS series
Ex: When the target temperature is 25°C (77°F)
Cooling
23°C (73.4°F): Thermostat OFF
22°C (71.6°F): Switch to heating
Heating
27°C (80.6°F): Thermostat OFF
28°C (82.4°F): Switch to cooling
FDXS series
Ex: When the target temperature is 25°C (77°F)
Cooling
23°C (73.4°F): Thermostat OFF
22°C (71.6°F): Switch to heating
Heating
26.5°C (79.7°F): Thermostat OFF
27.5°C (81.5°F): Switch to cooling
Target tempe 3.0˚C (+5.4˚F)
Heating Operation
Target temperature – 2.5˚C (–4.5˚F)
Cooling Operation
(R16965)
Target temperature – 2.0˚C (–3.6˚F)
= Thermostat OFF
Target tempe 2.0˚C (+3.6˚F)
= Thermostat OFF
Target tempe 2.5˚C (+4.5˚F)
Heating Operation
Target temperature – 2.5˚C (–4.5˚F)
Cooling Operation
(R16966)
Target temperature – 2.0˚C (–3.6˚F)
= Thermostat OFF
Target tempe 1.5˚C (+2.7˚F)
= Thermostat OFF