background image

Installer reference guide 

Daikin room air conditioner

FTXP50N2V1B
FTXP60N2V1B
FTXP71N2V1B

Summary of Contents for FTXP50N2V1B

Page 1: ...Installer reference guide Daikin room air conditioner FTXP50N2V1B FTXP60N2V1B FTXP71N2V1B...

Page 2: ...on right side right back or right bottom 26 6 4 3 To connect the piping on left side left back or left bottom 27 6 4 4 To check for water leaks 28 7 Piping installation 29 7 1 Preparing refrigerant pi...

Page 3: ...the unit 43 10 2 2 To place the adapter into the unit 44 10 2 3 To check the functionality of the adapter 45 10 3 To install the ONECTA app 45 11 Configuration 46 11 1 To set a different channel of t...

Page 4: ...ld use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Fo...

Page 5: ...ION Indicates a situation that could result in explosion WARNING Indicates a situation that could result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that could...

Page 6: ...aikin room air conditioner 4P518023 14L 2022 06 Symbol Explanation Indicates a figure title or a reference to it Example 1 3 Figure title means Figure 3 in chapter 1 Indicates a table title or a refer...

Page 7: ...ructions described in the Daikin documentation WARNING Tear apart and throw away plastic packaging bags so that nobody especially children can play with them Possible risk suffocation WARNING Provide...

Page 8: ...where there is a risk of fire due to the leakage of flammable gases example thinner or gasoline carbon fibre ignitable dust In places where corrosive gas example sulphurous acid gas is produced Corro...

Page 9: ...fects Provide space for expansion and contraction of long runs of piping Design and install piping in refrigerating systems such as to minimise the likelihood of hydraulic shock damaging the system Mo...

Page 10: ...2 Ceiling mounted unit a 4 6 13 4 4 6 180 4 8 14 6 4 8 196 5 0 15 8 5 0 213 1 842 5 2 17 1 1 842 5 2 230 1 843 3 64 5 4 18 5 1 843 28 9 5 4 248 2 0 3 95 5 6 19 9 2 0 34 0 5 6 267 2 2 4 34 5 8 21 3 2...

Page 11: ...Take sufficient precautions in case of refrigerant leakage If refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxy...

Page 12: ...ant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately If the...

Page 13: ...G After finishing the electrical work confirm that each electrical component and terminal inside the electrical components box is connected securely Make sure all covers are closed before starting up...

Page 14: ...io waves a distance of 1 meter may NOT be sufficient NOTICE ONLY applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of rever...

Page 15: ...ation 429 CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units DANGER RISK OF...

Page 16: ...Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING Use an all pole disconnec...

Page 17: ...t Prepare in advance the path along which you want to bring the unit to its final installation position When handling the unit take into account the following Fragile handle the unit with care Keep th...

Page 18: ...nual c General safety precautions d Titanium apatite deodorising filter and the silver particle filter Ag ion filter e Indoor unit fixing screw M4 12L Refer to 9 3 To fix the unit on the mounting plat...

Page 19: ...ection cable g Insulation tape 5 2 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation Operation mode Operation range Cooling a b Outdoor t...

Page 20: ...the piping on left side left back or left bottom 27 6 4 4 To check for water leaks 28 6 1 Preparing the installation site Choose an installation location with sufficient space to transport the unit in...

Page 21: ...following places because it may shorten the life of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present In places where a mineral oil mist spr...

Page 22: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover 6 2 3 To remove the front grille CAUTION Wear adequate personal protective equipment protective gl...

Page 23: ...ctrical wiring box cover a a c b a 1 3 2 a Tab b Protruding part on the top of the cover c Screw 6 3 Mounting the indoor unit In this chapter 6 3 1 To install the mounting plate 23 6 3 2 To drill a wa...

Page 24: ...Center of the unit 6 3 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat ele...

Page 25: ...to remove the pipe port cover as this would damage the front grille 6 4 Connecting the drain piping In this chapter 6 4 1 General guidelines 25 6 4 2 To connect the piping on right side right back or...

Page 26: ...socket nominal 13 mm a b c 18 a Drain hose supplied with the indoor unit b Drain socket with nominal 13 mm field supply c Ridgid polyvinyl chloride pipe field supply Condensation Take measures agains...

Page 27: ...om the right side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right s...

Page 28: ...A Left side piping B Left back piping C Left bottom piping a Remove the pipe port cover here for left side piping b Remove the pipe port cover here for left bottom piping 6 4 4 To check for water lea...

Page 29: ...d space except joints directly connecting the piping to the indoor units NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless...

Page 30: ...should be at least 20 mm to prevent condensation on the surface of the insulation 7 2 Connecting the refrigerant piping 7 2 1 About connecting the refrigerant piping Before connecting the refrigerant...

Page 31: ...ls e g mineral oils and moisture from mixing into the system Install the piping so that the flare is NOT subjected to mechanical stress Do NOT leave pipes unattended at the site If the installation is...

Page 32: ...as possible bending radius should be 30 40 mm or larger 7 2 5 To flare the pipe end CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refriger...

Page 33: ...flare connections 2 Wrap the refrigerant piping connection using vinyl tape overlapping at least half the width of the tape with each turn Keep the slit of the heat insulation pipe cover up Avoid wrap...

Page 34: ...e electrical wiring typically consists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 Connecting the electrical wiring to the...

Page 35: ...reaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer i...

Page 36: ...Item Tightening torque N m M4 X1M 1 2 M4 earth The earth wire between the wire retainer and the terminal must be longer than the other wires 1 3 8 1 3 Specifications of standard wiring components Comp...

Page 37: ...able c Wire guide 2 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the interconnect...

Page 38: ...s LAN adapter CANNOT be used together with other optional accessory 1 Remove the electrical wiring box cover see 6 2 4 To remove the electrical wiring box cover 423 2 Remove the wireless LAN adapter c...

Page 39: ...nt piping and the electrical wiring are finished Wrap refrigerant piping interconnection cable and drain hose together using insulation tape Overlap at least half the width of the tape with each turn...

Page 40: ...f the mounting plate Make sure that the wires do NOT get squeezed anywhere Note Take care that the interconnection cable does NOT get caught in the indoor unit 3 Press the bottom edge of the indoor un...

Page 41: ...then mount the front panel 9 4 3 To close the service cover 1 Place the service cover to its original place on the unit 2 Install 1 screw back on the service cover 9 4 4 To re install the front panel...

Page 42: ...rding to the definition of Directive 2014 53 EU and S I 2017 1206 Radio Equipment Regulations 2017 INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 10...

Page 43: ...To connect the wireless LAN adapter with the unit 1 Remove the tape holding the connecting cord connector a a Tape 2 Cut the clip and remove the connector from the protection sleeve b a a Protection...

Page 44: ...top of the lower case and press to close the box 7 Fix the upper adapter case with 2 screws accessory 2 10 2 2 To place the adapter into the unit 1 Place the wireless LAN adapter into the holder 2 Pre...

Page 45: ...022 06 10 2 3 To check the functionality of the adapter 1 Turn on the power supply and check that the RUN lamp of the product blinks 10 3 To install the ONECTA app 1 Open Google Play for appliances us...

Page 46: ...e careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position 4 P...

Page 47: ...4L 2022 06 8 When the setting is complete Keep pressed for about 5 seconds Result The user interface will return to the previous screen INFORMATION In case you could NOT complete the setting in time t...

Page 48: ...fore commissioning 1 After the installation of the unit check the items listed below 2 Close the unit 3 Power up the unit You read the complete installation instructions as described in the installer...

Page 49: ...t to make sure that all functions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can b...

Page 50: ...user Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in t...

Page 51: ...3 14L 2022 06 14 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation Units MU...

Page 52: ...parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Mea...

Page 53: ...V L Pilot lamp light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic rela...

Page 54: ...high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selec...

Page 55: ...lication explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions In...

Page 56: ...4P518023 14L 2022 06 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: