SiUS042113E
Troubleshooting
Part 6 Service Diagnosis
91
4.3 Freeze-up Protection Control/Heating Peak-cut Control
Error Code
A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 60 ~ 62°C (140 ~
144°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R21064)
YES
YES
NO
Caution
Provide s
u
fficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor
u
nit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the d
u
st acc
u
m
u
lation on
the indoor heat exchanger.
Is there any short circ
u
it?
Dirty?
Dirty?
Check the air passage.
Be s
u
re to t
u
rn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...