Field Settings
SiUS042113E
152
Part 7 Trial Operation and Field Settings
4. Field Settings
4.1 Temperature Display Switch
Procedure
Press the upper side of
Temp
button and
On
button at the same time for 5 seconds to change
the unit of temperature display.
4.2 When 2 Units are Installed in 1 Room
Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless
remote controller can be set for different address.
Procedure
1. Remove the battery cover of the remote controller, and cut the address jumper (J4).
2. Press the center of
Temp
button and
Mode
button on the remote controller at the same time.
3. Select
A
(address setting) with
Temp
or
Temp
button, and press
Mode
button to enter the
address setting mode.
Then, the indoor unit operation lamp blinks for 1 minute.
4. Press the indoor unit
ON/OFF
switch while the operation lamp is blinking.
If setting could not be carried out completely while the operation lamp was blinking, carry out
the setting process once again from the beginning.
After setting, press
Mode
button on the remote controller for 5 seconds to return to the
normal mode.
(R22009)
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...