Part 6 Service Diagnosis
141
5.9 Installation Condition Check
Check No.17
1
2
3
4
5
6
7
320 VDC
(R25288)
S70
PCB
Act
u
al rotation p
u
lse inp
u
t (0 ~ 15 VDC)
Rotation command voltage (0 ~ 6.5 VDC)
Control voltage 15 VDC
Installation condition check
OK
Check the allowable
dimensions of the air
s
u
ction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19394)
NG
YES
YES
NO
Is the discharged air
short-circ
u
ited?
NO
NO
YES
Is the o
u
tdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the o
u
tdoor heat
exchanger.
Change the installation
location or direction.
Check the o
u
tdoor temperat
u
re.
(The o
u
tdoor temperat
u
re
sho
u
ld be within the operation
range.)