• The precautions described herein are classified as WARNING and CAUTION. They both contain important information 

regarding safety. Be sure to observe all precautions without fail.

• Meaning of WARNING and CAUTION notices

WARNING

• The safety marks shown in this manual have the following meanings:

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate 

the air conditioner and take care of it with the aid of the operation manual.

• Ask your dealer or qualified personnel to carry out installation work. 

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.

• Install the air conditioner in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electric shocks or fire.

Safety Precautions (1)

WARNING

CAUTION

Failure to follow these instructions properly may result in personal injury or loss of life.

Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

Be sure to follow the instructions.

Be sure to establish an earth connection.

Never attempt.

DAIKIN AIR CONDITIONER

3P384095-2  M14B149

The two-dimensional bar code
is a manufacturing code.

• Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

• Electrical work must be performed in accordance with relevant local and national regulations and with the instructions in this installation manual. 

Be sure to use a dedicated power supply circuit only. Insufficient power supply and improper workmanship may result in electric shocks or fire.

• Use a cable of suitable length. Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the 

control box lid can be securely fastened. Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections or wires. Improper connections or securing of wires may result in abnormal heat build-up or fire.

• Install the air conditioner on a foundation strong enough to hold the weight of the unit. 

A foundation of insufficient strength may result in the equipment falling and causing injury.

• When installing or relocating the air conditioner, do not let any other substances besides R32, such as air, enter the refrigerant circuit. 

The presence of air or other foreign matter in the refrigerant circuit causes an abnormal pressure rise, which may result in equipment damage and even injury.

• If refrigerant gas leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fire.

• Be sure to earth the air conditioner.  

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.

• Be sure to install an earth leakage circuit breaker. Failure to install an earth leakage circuit breaker may result in electric shocks or fire.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, 

an operating gas appliance or an operating electric heater).

• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• The appliance must be installed, operated and stored in a room with a floor area larger than 3.9m

2

.

• Comply with national gas regulations.

• During installation, attach the refrigerant piping securely before operating the compressor. If the refrigerant pipes are not attached and the stop valve is 

open when the compressor is operated, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

• During pump down, stop the compressor before removing the refrigerant piping. If the compressor is still operating and the stop valve is open during pump down, 

air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

Read the precautions in this manual 

carefully before operating the unit.

This appliance is filled with R32.

• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas 

leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.

Safety Precautions (2)

A

D

G

K

B

E

H

L

C

F

M

1

9

2

1

1

1

2

1

3

3

1

Mounting plate

Dry batteries AAA. LR03 

(alkaline)

Operation manual

Mounting plate fixing 

screws M4 × 25L

Indoor unit fixing screws

M4 × 12L

Remote controller holder

Fixing screws for remote 

controller holder M3 × 20L

Screw cover

J

Insulation tape

Wireless remote controller

Titanium apatite photocatalytic

air-purifying filters

3

Installation manual

Accessories

Installation Tips (1)

1.

  Removing and installing the front panel

• 

Removal method

Hook fingers on the tabs on the left and right of the main body, and open until the 
panel stops. Slide the front panel sideways to disengage the front panel shaft. 
Then pull the front panel toward you to remove it.

• 

Installation method

Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly. 
Push the centre of the lower panel surface firmly to engage the tabs.

2.

  Removing and installing the front grille

• 

Removal method

1) Remove the front panel to remove the air filter.
2) Remove 6 screws from the front grille.
3) In front of the           mark on the front grille, there are 4 upper hooks. 

Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.

<When there is insufficient work space because the unit is close to ceiling>

Place both hands under the centre of the front grille, and while pushing up, 

pull it toward you.

• 

Installation method

1) 

Install the front grille and firmly engage the upper hooks (4 locations).

2) Install 6 screws of the front grille.
3) Install the air filter and then mount the front panel.

Be sure to wear protection 

gloves.

CAUTION

• Before choosing the installation site, obtain user approval.

1.

  Indoor unit

• 

The indoor unit should be positioned in a place where:

1) 

the restrictions on the installation requirements specified 

in the indoor unit installation drawings are met,

2)  both the air inlet and air outlet are unobstructed,

3)  the unit is not exposed to direct sunlight,

4)  the unit is away from sources of heat or steam,

5)  there is no source of machine oil vapour (this may 

shorten the indoor unit service life),

6)  cool (warm) air is circulated throughout the room,

7) 

the unit is away from electronic ignition type 

fluorescent lamps (inverter or rapid start type) as 

they may affect the remote controller range,

8) 

the unit is at least 1m away from any television or radio set 

(the unit may cause interference with the picture or sound),

9) 

the unit can be installed at the recommended height (2.5m),

10)  no laundry equipment is located.

2.

  Wireless remote controller

•  Turn on all the fluorescent lamps in the room, if any, 

and find a location where the remote controller signals 

are properly received by the indoor unit (within 7m).

Choosing an Installation Site



 mark area 

(4 locations)

Upper hook

1) Push up.

2) Pull toward you.

CAUTION

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.

• Tighten the flare nut as specified, such as with a torque wrench. 

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.

• Only qualified personnel can handle, fill, purge and dispose of the refrigerant.

N004

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate 

the piping to prevent condensation. Improper drain piping may result in indoor water leakage and property damage.

 This product is not designed for re-packing. In case of re-packing contact to Daikin dealer.

Push the front panel 
shaft of the front panel 

into the groove.

Push

down.

Upper hook

Indoor Unit Installation Drawings

INTELLIGENT EYE sensor

• 

Do not hit or forcefully push the intelligent-eye sensor. This can lead to damage and malfunction.

• 

Do not place large objects near the sensor. Also keep heating units or humidifiers outside the sensor’s detection area.

CAUTION

30mm or more 
from ceiling

INTELLIGENT EYE 
sensor

50mm or more 
from walls 
(on both sides)

Front panel

M4 × 16L

M4 × 16L

M4 × 16L

Screw cover (3 pcs)

M

Wrap the thermal insulation 

pipe with the finishing tape 

from bottom to top.

Cut thermal insulation 

pipe to an appropriate 

length and wrap it with 

tape, making sure that no 

gap is left in the insulation 

pipe’s cut line.

Caulk pipe 

hole gap 

with putty. 

A Mounting plate

Mounting plate fixing 

screws M4 × 25L (9 pcs)

B

The mounting plate 

should be installed on a 

wall which can support the 

weight of the indoor unit.

Air filters

The service lid is 
removable.

Opening method

1) Remove the service 

lid screws.

2) Pull out the service 

lid diagonally down 
in the direction of 
the arrow.

3) Pull down.

Service lid

The flare connection should 

be installed outdoors.

C Titanium apatite photocatalytic 

air-purifying filter (3 pcs)

Titanium apatite photocatalytic 

air-purifying filter

Filter frame

Air filter

Tab

 D  Wireless 
remote controller

 E  
Remote 
controller holder

Fixing screws for 

remote controller 
holder M3 × 20L 
(2 pcs)

F

Before screwing 
the remote 
controller holder 
to the wall, make 
sure that control 
signals are 
properly received 
by indoor unit.

1) 

Insert the tool into the groove of the front grille fixture.

How to remove front grille fixture

2) Turn the tool 90° in the direction of the arrow.

3) Take out the front grille fixture.

Bottom of indoor unit

Front grille fixture

Front grille fixture

How to attach the indoor unit.

Hook the tabs of the bottom frame

to the      mounting plate.

If the tabs are difficult to hook,

remove the front grille.

How to remove the indoor unit.

Push up the marked area (at the

lower part of the front grille) to

release the tabs. If it is difficult to

release, remove the front grille.

Front 

grille

A Mounting

plate

Tab

Bottom frame

Mark (rear side)

A

Unit dimensions 

Height

Width
Depth

340mm

1200mm

240mm

1.

  Installing the mounting plate

• The mounting plate should be installed on a wall which can support the weight of the indoor unit.

1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and 

mark the boring points on the wall.

2) Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions

Indoor Unit Installation (1)

2.

  Drilling a wall hole and installing wall embedded pipe

• For metal frame or metal board walls, be sure to use a wall embedded 

pipe and wall hole cover in the feed-through hole to prevent possible heat, 

electrical shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to 

prevent water leakage.

1) Drill a feed-through hole with a 80mm diameter through the wall at a 

downward angle toward the outside.

2) Insert a wall embedded pipe into the hole.

3) Insert a wall hole cover into wall pipe.

4) After completing refrigerant piping, wiring, and drain piping, caulk the pipe hole gap with putty.

3.

  Installing the indoor unit

3-1.  Right-side, right-back, or right-bottom piping

1) Attach the drain hose to the underside of the refrigerant pipes 

with an adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with  

     insulation tape.

3) Pass the drain hose and refrigerant pipes through the wall hole, 

then set the indoor unit on the mounting plate hooks by using the 

   markings at the top of the indoor unit as a guide.

4) Open the front panel, then open the service lid. 

(Refer to Installation Tips.)

5) Pass the inter-unit wire from the outdoor unit through the feed-

through wall hole and then through the back of the indoor unit. 

Pull them through the front side. 

  Bend the ends of cable tie wires upward for easier work in advance. 

(If the inter-unit wire ends are to be stripped first, bundle the wire 

lead ends with adhesive tape.)

6) Press the bottom frame of the indoor unit with both hands to set it 

on the mounting plate hooks. Make sure that the wire leads do 

not catch on the edge of the indoor unit.

J

Inside

Outside

Caulking(field supply)

Wall embedded pipe 
(field supply)

φ

80

Right-bottom 
piping

Right-back piping

Right-side piping

Bind refrigerant 
pipe and drain 
hose together with 

insulation tape.

J

Remove pipe port cover 
here for right-side piping.

Remove pipe port cover 
here for right-bottom piping.

Mounting plate

A

45

190

53

134

131

45

340

65.3

φ

80

161

182.5

89

φ

80

1200

47

554

unit: mm

Use a tape 
measure 
as shown.
Position 
the end of 
the tape 
measure 
at  

  .

Gas pipe end 

Liquid pipe end

Place the pipe port cover 
in this pocket.

Through-the-wall 
hole 

φ

80mm

Drain hose 
position

Removed pipe 
port cover 

The removed pipe port 
cover can be kept in the 
mounting plate pocket.

Recommended mounting plate 
retention spots (9 spots in all)

(Bolt size: M10)

(Bolt size: M10)

(Bolt size: M10)

Place a leveler on these tabs.

A

Mounting 
plate

Wire guide

When stripping the 
ends of inter-unit 
wire in advance, 
bundle the wire 
lead ends with tape.

Hang indoor unit’s hook here.

Inter-unit 
wiring

Mounting 
plate

A

Wall hole cover
(field supply)

Indoor Unit Installation (2)

3-2.  Left-side, left-back, or left-bottom piping

1) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

2) Be sure to connect the drain hose to the drain port in 

place of the drain plug.

3) Shape the refrigerant pipes along the pipe path 

marking on the mounting plate.

4) Pass the drain hose and refrigerant pipes through 

the wall hole, then position the indoor unit on the 

mounting plate hooks, using the    markings at 

the top of the indoor unit as a guide.

5) Pull in the inter-unit wire.

6) Connect the refrigerant pipes.

7) In case of pulling the drain hose through the back of the indoor 

unit, wrap the refrigerant pipes and drain hose together with 

 J  insulation tape as shown in the right figure.

8) While exercising care so that the inter-unit wiring does not catch the 

indoor unit, press the bottom edge of the indoor unit with both hands until 

it is firmly caught by the mounting plate hooks.  Secure the indoor unit to 

the mounting plate with the  H

  indoor unit fixing screws (M4 × 12L).

3-3.  Wall embedded piping

Follow the instructions given under left-side, left-back, or 

left-bottom piping.

1) Insert the drain hose to this depth so it won’t be pulled out of 

the drain pipe.

4.

 Wiring

 

1) Strip wire ends (20mm).

2) Match wire colours with terminal numbers on the indoor and 

outdoor unit’s terminal blocks and firmly secure the wires in 

the corresponding terminals with the screws.

3) Connect the earth wires to the corresponding terminals.

4) Pull the wires lightly to make sure they are securely 

connected, then secure them with the wire retainer.

5) In case of connecting to an adapter system, run the remote 

controller cable and attach the S21. 

(Refer to “

5. When connecting to an HA system

”.)

6) Shape the wires so that the service lid fits securely, then close the 

service lid.

• 

Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock,or fire.

• 

Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, 
etc., from the terminal block.) Doing so may cause electric shock or fire.

• 

Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

WARNING

How to set the drain hose.

• 

Insert drain hose and tighten fixing screw.

  Forgetting to attach this may cause water leakages.
  The drain hose is on the back of the unit.

How to set the drain plug.

Front side of unit

Drain hose attachment position

Attachment on the left side

Drain hose

Fixing screw

Attachment on the right side (factory default)

Drain hose

Fixing screw

Remove pipe port cover here for left-bottom piping.

Remove pipe port 

cover here for 
left-side piping.

Left-bottom piping

Left-side 

piping

Left-back 

piping

No gap

Insert a hexagon 

wrench (4mm)

Wrap     insulation tape 
around the bent portion of the 
refrigerant pipe. 
Overlap at least half the width 
of the     insulation tape with 
each turn.

Drain 

hose

Caulk this hole 

with putty or 

caulking material.

Bind with vinyl 

tape.

Mounting plate

Refrigerant

pipes

Drain hose

Bottom frame

M4 

×

 12L (3 locations)

Inter-unit wire

Mounting

plate

Inner wall

Vinyl chloride 
drain pipe 

(VP-30)

Drain hose

50mm 

or more

Insert drain hose to this 
depth so it won’t be 
pulled out of drain pipe.

Outer wall

Shape wires so 

that the service 

lid will fit securely.

Terminal block
Electrical wiring box

Wire retainer

Firmly secure the wire 

retainer so that wires 

sustain no external stress.

Use the 

specified 

wire type.

Do not apply 
lubricating oil 

(refrigerant oil) to 

the drain plug when 
inserting it.
The application of 
lubrication oil to the 
drain plug will 
deteriorate the plug 
to cause drain 
leakage from the 
plug.

A

A

H

J

J

1

2

3

1 2 3

L

N

Inter-unit wire 
4-core 1.5mm² or more 

60245 IEC 57

Firmly fix the wires with 

the terminal screws.

Outdoor unit

Indoor 
unit

Firmly fix the wires with 

the terminal screws.

5.

  When connecting to an HA system

1) Remove the front grille. 

(6 screws, 3 front grille 

fixtures)

2) Remove the electrical 

wiring box. (1 screw)

3) Remove the metal plate 

electrical wiring box cover. 

(4 tabs)(See 

Fig.1

)

4) Attach the connection 

cord to the S21 connector 

and pull the harness out 

through the notched part in the figure. (See 

Fig.2

)

5) 

Replace the electrical wiring box cover as it was, and pull the harness around, as shown in the figure.(See 

Fig.3

)

Indoor Unit Installation (3)

Refrigerant Piping Work (1)

6.

  Drain piping

1) Connect the drain hose, as described below.

2) Remove the air filters and pour some water 

into the drain pan to check the water flows 

smoothly.

3) 

When drain hose requires extension, obtain an 

extension hose with an inner diameter of 16mm.

Be sure to thermally insulate the indoor

section of the extension hose.

4) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 

hose attached to the indoor unit as with embedded 

piping work, use any commercially available drain 

socket (nominal diameter 13mm) as a joint.

1.

  Flaring the pipe end

1) Cut the pipe end with a pipe cutter.

2) 

Remove burrs with the cut surface facing 

downward so that the chips do not enter the 
pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring is properly made.

• 

Do not use mineral oil on flared part.

• 

Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.

• 

Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.

• 

Never install a drier to this R32 unit in order to guarantee it’s lifetime.

• 

The drying material may dissolve and damage the system.

• 

Incomplete flaring may cause refrigerant gas leakage.

WARNING

(Cut exactly at 

right angles.)

 Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R32 or R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 

a perfect circle.

Make sure that the 
flare nut is fitted.

Fig.1

Fig.2

Fig.3

The drain hose should 

be inclined downward.

No trap is permitted.

Do not put the end 

of the hose in water.

Indoor unit 

drain hose

φ

16

Extension drain hose

Heat insulation tube
(field supply)

Drain hose supplied with 
the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

φ

16

Screw

Pull

Pull

Slide

Tab

Tab

Slide

Metal plate 
electrical cover

Main body

HA connector
(S21)

HA connector
(S21)

Lay the HA cord as 

shown in the figure.

Refrigerant Piping Work (2)

2.

  Refrigerant piping

2-1.  Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.

2) All pipe bends should be as gentle as possible. Use a pipe 

bender for bending. 

2-2.  Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:

1)  Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

  Refrigerant gas pipe’s surface temperature reaches 110°C max.

  Choose heat insulation materials that will withstand this temperature.

2) 

Be sure to insulate both the gas and liquid piping and observe the

insulation dimensions as below.

3)  Use separate th

ermal insulation pipes for gas and liquid refrigerant pipes.

• Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully 

with the torque wrenches.

• Refrigerant oil for R410A can also be used for application to the inner flare.

• 

Use the flare nut fixed to the main unit.

   (This is to prevent cracking of the flare nut as a result of deterioration over time.)

• 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare.

   (Use refrigeration oil for R32.)

• 

Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

CAUTION

Wall

If no flare cap is 

available, cover 

the flare mouth 

with tape to keep 

dirt or water out.

Be sure to 

place a cap.

Rain

Flare nut tightening torque

Gas side

Liquid side

61.8-75.4N 

 m

(630-770kgf 

 cm)

14.2-17.2N 

 m

(144-175kgf 

 cm)

15.9mm

6.4mm

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration oil to the 
inner surface of the flare.

Do not apply refrigeration 
oil to the flare nut to avoid tightening 
with excessive torque.

Apply oil

Torque wrench

Piping union

Flare nut

Spanner

Tighten

Gas pipe

Inter-unit wire

Liquid pipe

Gas pipe 

insulation

Liquid pipe 

insulation

Finishing tape Drain hose

Gas side

Piping size

O.D. 15.9mm

O.D. 6.4mm

50mm or more

30mm or more

1.0mm (C1220T-O)

0.8mm (C1220T-O)

I.D. 16-20mm

I.D. 8-10mm

10mm Min.

Minimum bend radius

Piping thickness

Thermal insulation size Thermal insulation

thickness

Liquid side

Trial Operation and Testing

Test items

Incomplete cooling/heating function

No refrigerant gas leaks.

Draining line is properly installed.

Indoor and outdoor units are installed properly on 
solid bases.

Refrigerant gas and liquid pipes and indoor drain 
hose extension are thermally insulated.

Fall, vibration, noise

Water leakage

Water leakage

System is properly earthed.

Electrical leakage

Indoor unit properly receives remote controller 
commands.

No operation

Incomplete cooling/heating function

Incomplete cooling/heating function

The specified wires are used for inter-unit wiring 

connections.

No operation or burn damage

Symptom

Check

     will appear when the MODE button is pressed.*

No heating

Indoor or outdoor unit’s air inlet or air outlet are 
unobstructed.

* Check that the jumper (J8) has not been cut. If it has been 

cut, contact the service shop.

Stop valves are opened.

1.

  Trial operation and testing

• Trial operation should be carried out in either COOL or HEAT operation.

 

1-1 Measure the supply voltage and make sure that it is within the specified range.

 

1-2 In COOL operation, select the lowest programmable temperature; in HEAT operation,

select the highest programmable temperature.

1-3 Carry out the trial operation in accordance with the operation manual to ensure that all 

functions and parts, such as louvres movement, are working properly.

• 

For protection, the system disables restart operation for 3 minutes after it is turned off.

• When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on, in 

some cases no air will be output for about 10 minutes in order to protect the air conditioner.

1-4 After trial operation is complete, set the temperature to a normal level (26°C to 28°C in COOL 

operation, 20°C to 24°C in HEAT operation).

• When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, set it to the trial 

operation mode using the following method.

1)  Press         and select the trial operation (COOL or HEAT).
2)  Press         to turn on the system.
3)  Press both of      and         at the same time. 
4)  Press      , select “    ”,and press         for confirmation.
• Trial operation will stop automatically after about 30 minutes.

  To stop the operation, press        .

• Some of the functions cannot be used in the trial operation mode.

• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

Jumper (J8)

2.

  Test items

01_EN_3P384095-2.indd   1

11/4/2014   1:08:19 PM