SiBE041401E
Trial Operation
Trial Operation and Field Settings
106
2. Trial Operation
Outline
Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C); in heating
operation, select the highest programmable temperature (30°C).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26°C ~ 28°C in
cooling, 20°C ~ 24°C in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
ARC466 Series
(1) Press the
On/Off
button to turn on the system.
(2) Press the center of the
Temp
button and the
Mode
button at the same time.
(3) Select
T
(trial operation) with the
Temp
▲
or
Temp
▼
button.
(4) Press the
Mode
button to start the trial operation.
(5) Press the
Mode
button and select operation mode.
(6) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit trial
operation, press the
On/Off
button.
(R19935)
(2) (4) (5)
(1) (6)
(2) (3)
(3)
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...