SiBE041525F
Check
Service Diagnosis
82
5.5
Four Way Valve Performance Check
Check No.13
5.6
Inverter Unit Refrigerant System Check
Check No.14
(R21439)
NO
YES
YES
NO
Turn off the power. Then, turn on
the power to restart the system.
Disconnect the four way valve coil
from the connector and check the
continuity.
Start heating operation.
∗
Four way valve coil
Cooling / Dry: Not energized
Heating: Energized
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
coil.
Replace the four way valve.
Four way
valve coil resistance at
1000 ~ 2000
Ω
?
S80
voltage at 220 - 240
VAC with compressor
on? (Fig. 1)
(R11904)
(Fig. 1)
Voltage at S80
220 - 240 VAC
Time
Compressor
ON
Refrigerant system check
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (
U0
).
(R22766)
YES
NO
Reconnect the discharge
pipe thermistor.
Replace the refrigerant.
Is the
discharge pipe
thermistor disconnected
from the holder?
Summary of Contents for FTX20K2V1B
Page 12: ...SiBE041525F 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 15: ...SiBE041525F Specifications 4 Part 2 Specifications 1 Specifications 5...
Page 16: ...Specifications SiBE041525F 5 Specifications 1 Specifications See corresponding databook...
Page 51: ...SiBE041525F Remote Controller 40 Part 5 Remote Controller 1 Remote Controller 41...