Check
SiENBE12-713
276
Service Diagnosis
6. Check
6.1
How to Check
6.1.1 Fan Motor Connector Output Check
Check No.01
1. Check connector connection.
2. Check motor power supply voltage output (pins 4-7 and 4-8).
3. Check motor control voltage (pins 4-3).
4. Check rotation command voltage output (pins 4-2).
5. Check rotation pulse input (pins 4-1).
Check No.02
1. Check connector connection.
2. Check motor control voltage output (pins 2-1).
6.1.2 Limit Switch Continuity Check
Check No.03
Remove the front grille. The limit switch is located at the left side of the drain pan assembly.
Check the continuity of the switch connection.
∗
The shutter can be opened and closed with hand. Keep the shutter open and closed all the
way for each continuity check steps.
7
6
5
4
3
2
1
Motor power supply voltage
Unused
Unused
P.0V (reference potential)
Motor control voltage (15 VDC)
Rotation command voltage (1~ 5 VDC)
Rotation pulse input
S1 or S301
8
7
6
5
4
3
2
1
Motor power supply voltage
Unused
Unused
Unused
P.0V (reference potential)
Motor control voltage (15 VDC)
Rotation command voltage (1 to 5 VDC)
Rotation pulse input
S302
(R4684)
5
4
3
2
1
Motor power supply voltage
Unused
Unused
P.0V (reference potential)
Motor control power supply
S202
(R1073)
Tester
Limit switch
Forward
Upward
Shutter status
Continuity
Closed
No continuity
Open
Continuity
(Q0363)
Summary of Contents for FTKS20D3VMW
Page 11: ...Introduction SiENBE12 713 x...
Page 47: ...Specifications SiENBE12 713 36 Specifications...
Page 113: ...Control Specification SiENBE12 713 102 Function and Control...
Page 235: ...Instruction SiENBE12 713 224 System Configuration...
Page 297: ...Check SiENBE12 713 286 Service Diagnosis...
Page 316: ...SiENBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points...