SiMT041509E
Troubleshooting
Service Diagnosis
54
4.2
Indoor Unit PCB Abnormality
Error Code
A1
Method of Error
Detection
The system checks if the circuit works properly within the microcomputer of the indoor unit.
Error Decision
Conditions
The system cannot set the internal settings.
Supposed
Causes
Wrong models interconnected
Defective indoor unit PCB
Disconnection of connector
Reduction of power supply voltage
Troubleshooting
Note:
Check the following connector.
Check the connection of
connectors (See Note.).
Correct the connection.
OK?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Error repeats?
Combination of
the indoor and outdoor
unit matched?
YES
NO
NO
YES
NO
NO
YES
(R20486)
Caution
∗
To secure the connection,
once disconnect the connector
and then reconnect it.
YES
NO
YES
NO
YES
NO
YES
Match the compatible
models.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Completed.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Model Type
Connector
Wall mounted type
Terminal board ~ Control PCB (H1, H2, H3)
Summary of Contents for FTKM18PVMK
Page 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Page 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...