OUTDOOR UNIT INSTALLATION
Install as described in the installation manual supplied with the outdoor unit.
REFRIGERANT PIPING WORK
See the installation manual supplied with the outdoor unit.
1.
FLARING THE PIPE END
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
Warning
Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
Do never install a dryer to this R410A unit in order to guarantee its lifetime.
The drying material may dissolve and damage the system.
Incomplete flaring may cause refrigerant gas leakage.
2.
REFRIGERANT PIPING
1) To prevent gas leakage, apply refrigeration machine oil on both
inner and outer surfaces of the flare. (Use refrigeration oil for
R410A)
2) Align the centres of both flares and tighten the flare nuts 3 or 4
turns by hand. Then tighten them fully with the torque wrenches.
• Use torque wrenches when tightening the flare nuts to prevent
damage to the flare nuts and escaping gas.
Caution
Overtightening may damage the flare and cause leaks.
3) After the work is finished, make sure to check that there is no
gas leak.
4) After checking for gas leaks, be sure to insulate the pipe connections.
• Insulate using the insulation for fitting included with the liquid and gas pipes. Besides, make sure the insulation for fitting
on the liquid and gas piping has its seams facing up.
(Tighten both edges with clamp.)
• For the gas piping, wrap the medium sealing pad over the insulation for fitting (flare nut part).
A
A
Die
Flaring
Conventional flare tool
Wing-nut type (Imperial-type)
Clutch-type (Ridgid-type)
Flare tool for R410A
Clutch-type
Set exactly at the position shown below.
1.5-2.0mm
1.0-1.5mm
0-0.5mm
Make sure that the
flare nut is fitted.
The pipe end must
be evenly flared in a
perfect circle.
Flare’s inner surface
must be flaw-free.
Remove burrs
(Cut exactly at right angles.)
Check
Flare nut tightening torque
Gas side
Liquid side
Ø9.5
Ø12.7
Ø6.4
33-39N•m
50-60N•m
15-17N•m
Spanner
Flare nut
Piping union
Torque wrench
Coat here with refrigeration
machine oil