Frequency Regulating Functions
SiBE28-804
74
Functional Description
4.10 Inverter Cooling Fin Temperature Control
Outline
This control will restrict the compressor upper limit frequency in order to protect the electronic
components in the switch box from overheating (L4-error activation).
By lowering the compressor frequency, the current drawn by the compressor will be reduced
and as a result the temperature inside the switch box will drop.
Flow chart
Parameters
Fin Temperature
≤
B°C lasts for 2 minutes
Normal operation
Compressor frequency
–1 step/2 min
Compressor frequency
–1 step/6 sec
Inverter fin temperature
≥
A°C
Inverter upper limit frequency
= Maximum frequency
RZQ71C7,
RZQS71·100C7V1B
RZQ100~140C7,
RZQS125·140C7V1B
A°C
82°C
83°C
B°C
79°C
80°C