SiBE28-804
Installation and Service Space (RZQ100~140C7, RZQS125~140C7)
Appendix
245
2.2
Stacked
The illustration below shows the required installation and service space (mm). The values in
brackets are for RZQ100~140, RZQS125~140 class.
Do not stack more than one unit.
± 100 mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
2.3
Multiple Rows
The illustration below shows the required installation and service space (mm). The values in
brackets are for the 100~140 class.
Relation of dimensions of H, A and L are shown in the table below.
Obstacles exist in front of the outlet side
Obstacles exist in front of the air inlet
L
A
L
≤
H
0 < L
≤
1/2H
150 (250)
1/2H < L
200 (300)
H < L
installation impossible
Installation of one unit per row
Installing multiple units (2 units or more)
in lateral connection per row
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...