SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
207
5.33 “
LC
” Malfunction of Transmission System (between
Control and Inverter PC Board)
Remote
Controller
Display
LC
Applicable
Models
RZQ(S)71~140
Method of
Malfunction
Detection
Checks and sees whether transmission between control and inverter PC board is carried out
normally.
Malfunction
Decision
Conditions
When the transmission is not carried out in a specified period of time or longer
Supposed
Causes
Incorrect transmission wiring between control and inverter PC board/insufficient contact in
wiring
Faulty control and inverter PC board
External factors (noise, etc.)
Faulty outdoor Fan motor
Faulty of fan motor connector contact