Troubleshooting by Remote Controller Display / LED Display
SiBE28-804
164
Troubleshooting
5.9
“
A7
” Swing Flap Motor Malfunction / Lock
Remote
Controller
Display
A7
LED indications
The table below shows the LED indications.
Error generation
The error is detected by the limit switch when the motor turns.
When ON/OFF of the microswitch for position detection cannot be reversed eventhough the
swing flap motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
The possible causes are:
Failure of swing flap motor
Failure of microswitch
Failure of connector connection
Failure of indoor unit PC board
Operation
HAP (green)
HBP (green)
Normal
5
5
Malfunctioning
5
5