SiUS091628EA
Troubleshooting
Service Diagnosis
84
4.18 Input Overcurrent Detection
Error Code
E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor running.
Error Decision
Conditions
The current exceeds about 12.0 ~ 12.5 A (depending on the model) for 2.5 seconds with the
compressor running.
(The upper limit of the current decreases when the outdoor temperature exceeds a certain level.)
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15
Refer to P.104
Check No.17
Refer to P.107
Check No.18
Refer to P.107
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
∗
An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Any LED off?
Input current flowing
above its stop level?
∗
Inverter analyzer:
RSUK0917C
Summary of Contents for FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU
Page 12: ...SiUS091628EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS091628EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS091628EA 109 Service Diagnosis 15 18 class R20701 1 2 3 4 Multimeter...
Page 122: ...Check SiUS091628EA 111 Service Diagnosis 15 18 class R20704 W V U DC_P1 DC_N1...