Field Settings
SiUS091628EA
123
Trial Operation and Field Settings
4.4
Address and MAIN/SUB Setting for Wireless Remote
Controller
Outline
If setting multiple wireless remote controllers to operate in one room, perform address setting
for the receiver and the wireless remote controller.
If using both a wired remote controller and a wireless remote controller with 1 indoor unit,
change the MAIN/SUB switch of the transmitter board.
Transmitter
Board
Wireless address switch
Set the wireless address setting switch (SS2) on the transmitter board according to the table below.
MAIN/SUB switch
When using both wired and wireless remote controllers for 1 indoor unit, the wired remote controller
should be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the transmitter board to SUB.
Unit No.
No.1
No.2
No.3
Wireless address switch
(SS2)
123
(S1935)
123
(S1936)
123
(S1937)
MAIN
SUB
MAIN/SUB switch (SS1)
(R24062)
MS
(R24063)
MS
(R24374)
SS2
SS1