background image

Installation manual

3

FDYP125~2 FDQ125~250B8V3B

Split System air conditioners

4PW23694-1A

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories, refer to the instruction manual
of each optional accessory. Depending on the field conditions, it may
be easier to install optional accessories before the indoor unit is
installed.

1.

Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using a nut and washer from the upper and lower
sides of the hanger bracket.

2.

Do not install the unit tilted.
(If the unit is tilted against condensate flow, water can drip out of
the drain pan).

Check if the unit is levelled at all four corners with a water level (1) or
a water-filled vinyl tube (2) (Refer to 

figure 3

).

3.

Tighten the upper nut.

4.

An air filter is installed to prevent dust accumulation on the heat
exchanger. This will prolong the lifetime of the unit.

5.

Connect the air inlet to the air inlet ducting and the air outlet to
the air outlet ducting. Always provide a flexible connection
between the ducting flanges of the air conditioner and the ducts
to prevent vibrations and noise generation.

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, see the installation manual
attached to the outdoor unit.

When installing field piping, take the following items into
consideration:

The outdoor unit is charged with refrigerant.

Use a pipe cutter and flare suitable for the used refrigerant.

The liquid line must be connected to the air conditioning unit via
a flare connection. The gas line must be welded directly to the
air conditioning unit piping. In case of a 125 unit, both the liquid
line and the gas line must be connected to the air conditioning
via a flare connection.

In case of flare connections, flare the pipe end neatly to avoid
refrigerants leaks.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit (Refer to

figure 4

).

Refer to the table below for the dimensions of flare nut spaces.

Because R407C/R410A refrigerant is used, apply ether or ester
oil around the flare portions before connecting.
Coat here with ether oil or ester oil

Refer to the table above to determine the proper tightening
torque. (Overtightening may damage the flare and cause leaks.)

Check the pipe connector for gas leaks.

Only wrap the gas line side of the insulation for fitting (union)
with the sealing pad (attached).

Use copper alloy seamless pipes (ISO 1337).

V

ACUUM

 

DRYING

 

OF

 

INSTALLATION

Refer to the installation manual of the outdoor unit.

D

RAIN

 

PIPING

 

WORK

Ensure that a protective guard is installed in front of the air
outlet to prevent that the fan blades can be touched. The
protection must comply with relevant local and national
regulations.

All field piping (liquid line and gas line between the
condensing and the air conditioning unit) must be installed
by a licensed refrigeration technician and must comply with
relevant local and national regulations.

1

Piping union

2

Spanner

3

Flare nut

4

Torque wrench

1

2

3

1

Field procurement.

2

Washer for hanger bracket

3

Tighten (double nut)

Pipe 

gauge

Tightening torque

Flare dimension A (mm)

Flare shape

R407C

R410A

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.3~8.7

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.0~12.4

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

15.4~15.8

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

18.6~19.0

19.3~19.7

Ø19.1

97.2~118.6 N•m 

(990~1210 kgf•cm)

22.9~23.3

Arrange the drain hose to ensure smooth drainage.
Incomplete drainage may cause the building to
become wet.

The drain hose must slope downward to the outdoor
side.

Never put the end of the drain into water.

A trap to prevent bad odours is allowed.

If you extend the drain hose always insulate it up to
the outdoor side with polyethylene foam insulation
material (field supplied).

To  ensure a downward slope of minimum 1:100,
install hanging bars every 1 to 1.5 m.

If unifying multiple drain pipes, install pipes shown in
the figure above.

R0.4~0.8

45

° ±

2

90

°±

2

A

100

Summary of Contents for FDQ125B8V3B

Page 1: ...INSTALLATION MANUAL FDYP125B8V1 FDYP200B8V1 FDYP250B8V1 FDQ125B8V3B FDQ200B8V3B FDQ250B8V3B Split System air conditioners ...

Page 2: ... 2 2 1 4 5 3 1 2 4 1440 602 125 class 840 200 250 class P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 P1 P2 P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 7 P1 P2 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 2 1 1 2 3 4 5 6 7 8 9 ...

Page 3: ... atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus 23 tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un citiem normatīviem dokumentiem 24 sú v zhode s nasledovnou ými normou ami alebo iným i normatívnym i dokumentom ami za predpokladu že sa používajú v súlade s našim návodom 25 ürünün talimatları...

Page 4: ...maintenance and service can be ensured Refer to figure 1 service space The power supply intake 1 the drain connection 2 gas pipe 3 and liquid pipe 4 connection should always be accessible for maintenance and service Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual for the outdoor unit Where there is no danger of fire due to leaka...

Page 5: ... in places exposed to the air flow from the unit or under the indoor unit It may cause incomplete combustion or deformation of the unit due to the heat Tick when checked Is the indoor unit fixed firmly The unit may fall down vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Con...

Page 6: ...cting or disconnecting pipes to from the unit Refer to figure 4 Refer to the table below for the dimensions of flare nut spaces Because R407C R410A refrigerant is used apply ether or ester oil around the flare portions before connecting Coat here with ether oil or ester oil Refer to the table above to determine the proper tightening torque Overtightening may damage the flare and cause leaks Check ...

Page 7: ...e interconnection wiring from outdoor to indoor to the 1 2 3 terminal 1 using a separate power supply of the indoor unit fan motor to the L N terminal Remote controller code Connect the cords to the remote controller terminal P1 P2 No polarity 2 Precautions Do not clamp remote controller cords together with the other wiring Doing so may cause malfunction Do not place the controller where it is exp...

Page 8: ...rotect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the remote controller and start operation by pushing ON OFF button 5 Press Inspection Test Operation button 4 times and operate at Test Operation mode for 3 minutes 6 Press Inspection Test Operation button and operate normally 7 Confirm function...

Page 9: ...or Sky Air series only for FDYP125 250 X33A Connector Adaptor for wiring X40A Connector remote on off forced off X60A X61A Connector interface adaptor for Sky Air series only for FDQ Wired remote controller BS1 ON OFF button BS2 Timer mode start stop button BS3 BS8 Programming timer button BS4 Temperature setting button up BS6 Operation mode selector button BS7 Timer on off button BS9 Temperature ...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23694 1A ...

Reviews: