Troubleshooting for FDMQ Series
Part 6 Service Diagnosis
142
6.4 Indoor Fan PCB Abnormality
Error Code
A8
Method of Error
Detection
Microcomputer checks the voltage state of the fan PCB.
Error Decision
Conditions
Overvoltage or voltage drop is detected on the fan PCB.
Supposed
Causes
Defective fan PCB
External factor such as noise
Troubleshooting
R6000549
Caution
Be sure to turn off the power switch before connecting
or disconnecting connectors, or parts may be damaged.
Check for the indoor unit control
PCB (A1P) and the fan PCB
(A2P).
Connect the connector correctly.
NO
YES
YES
Is the
connector X3A on
the fan PCB connected
correctly?
Connect the connector correctly.
NO
YES
Is the
connector X70A on
the indoor unit control PCB
connected correctly?
Replace the harness.
YES
Is the harness
connecting X3A and X70A
broken?
NO
NO
Remove the external factor.
YES
Is there any external
factor such as noise?
Normal.
NO
Error is displayed
again.
Turn OFF the power supply
and then turn it ON again.
Start operation with the
remote controller.
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...