11 Technical data
Installer and user reference guide
21
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12
11.3
Service space: Indoor unit
▪
Spacing
. Mind the following requirements:
(mm)
≥1500
≥2000
≥4000
≥1500
A
B
C
b
a
d
a
c
A
Minimum distance to the wall (see below)
B
Minimum and maximum distance to the floor (see below)
C
≥298 mm
: In case of installation with standard decoration
panel
≥348 mm
: In case of installation with fresh air intake kit
≥378 mm
: In case of installation with self-cleaning
decoration panel
a
Indoor unit
b
Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c
Air fan
d
Static volume (example: table)
▪
A: Minimum distance to the wall
. Depends on the air flow
directions towards the wall.
≥1500
≥500
≥200
a
A
A
A
b
c
a
Air outlet and corners open
b
Air outlet closed, corners open (optional blocking pad kit
required)
c
Air outlet and corners closed (optional blocking pad kit
required)
▪
B: Minimum and maximum distance to the floor
:
▪ Minimum: 2.5 m to avoid accidental touching.
▪ Maximum: Depends on the air flow directions and the capacity
class. Also make sure the "Ceiling height" field setting
corresponds with the actual situation. See
.
If air flow direction…
Then B
FCAHG71
FCAHG100~140
All-round
≤3.5 m
≤4.2 m
4-way
(a)
≤4.0 m
≤4.5 m
3-way
(a)
≤3.5 m
≤4.2 m
(a)
Optional blocking kit required
11.4
Components: Indoor unit
f
g
h
i
c
b
a
e
d
a
Switch box
b
Gas pipe connection
c
Liquid pipe connection
d
Drain pipe connection (VP25)
e
Drain pump
f
Float switch
g
Fan motor
h
Heat exchanger
i
Hanger bracket
11.5
Piping diagram: Indoor unit
b
a
c
d
a
Liquid pipe connection
b
Gas pipe connection
c
Filter
d
Heat exchanger