Check
SiBE12-713
284
Service Diagnosis
6.1.13 Main Circuit Electrolytic Capacitor Check
Check No.14
Checking the main circuit electrolytic capacitor
z
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
z
If unavoidably necessary to touch a live part, make sure there is no DC voltage using the
tester.
z
Check the continuity with the tester. Reverse the pins and make sure there is continuity.
6.1.14 Turning Speed Pulse Input on the Outdoor Unit PCB Check
Check No.15
<Propeller fan motor>
Make sure the voltage of 320±30V is being applied.
(1) Stop the operation first and then the power, and disconnect the connector S70.
(2) Make sure there is about DC 320 V between pins 4 and 7.
(3) With the system and the power still off, reconnect the connector S70.
(4) Make a turn of the fan motor with a hand, and make sure the pulse (0-15 V) appears twice at
pins 1 and 4.
If the fan motor protection fuse is blown out, the outdoor-unit fan may also be in trouble. Check
the fan too.
If the voltage in Step (2) is not applied, it means the PCB is defective. Replace the PCB.
If the pulse in Step (4) is not available, it means the Hall IC is defective. Replace the DC fan
motor.If there are both the voltage (2) and the pulse (4), replace the PCB.
∗
Propeller fan motor : S70
1
2
3
4
5
6
7
DC320V
S70
PCB
Turning speed pulse input (0-15 V)
15V
(R5223)
Summary of Contents for F-Series
Page 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Page 11: ...Introduction SiBE12 713 x ...
Page 47: ...Specifications SiBE12 713 36 Specifications ...
Page 113: ...Control Specification SiBE12 713 102 Function and Control ...
Page 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Page 235: ...Instruction SiBE12 713 224 Operation Manual ...
Page 297: ...Check SiBE12 713 286 Service Diagnosis ...
Page 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...