Troubleshooting
SiBE12-713
236
Service Diagnosis
5.3
Indoor Unit PCB Abnormality
Remote
Controller
Display
A1
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by indoor unit.
Malfunction
Decision
Conditions
When there is no zero-cross detection in approximately 10 continuous seconds.
Supposed
Causes
Faulty indoor unit PCB
Faulty connector connection
Troubleshooting
Note:
Connector Nos. vary depending on models.
Control connector
Connector connection check
(note).
YES
Is it normal?
NO
Correct connections.
Replace PCBs.
(R1400)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Model Type
Connector No.
Wall Mounted Type 20 / 25 / 35 class Terminal strip~Control PCB
Wall Mounted Type 50 / 60 / 71 class Terminal strip~Control PCB
Duct Connected Type
Terminal strip~Control PCB
Floor / Ceiling Suspended Dual Type S37
Floor Standing Type
Terminal strip~Control PCB
Summary of Contents for F-Series
Page 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Page 11: ...Introduction SiBE12 713 x ...
Page 47: ...Specifications SiBE12 713 36 Specifications ...
Page 113: ...Control Specification SiBE12 713 102 Function and Control ...
Page 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Page 235: ...Instruction SiBE12 713 224 Operation Manual ...
Page 297: ...Check SiBE12 713 286 Service Diagnosis ...
Page 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...