SiBE12-713
Code Indication on the Remote Controller
Service Diagnosis
233
4. Code Indication on the Remote Controller
4.1
Error Codes and Description of Fault
Code Indication Description of Problem
System
00
Normal
U0
Insufficient gas
U2
Low-voltage detection or over-voltage detection
U4
Signal transmission error (between indoor and outdoor units)
U7
Signal transmission error (on outdoor unit PCB)
UA
Unspecified voltage (between indoor and outdoor units)
UH
Anti-icing function in other rooms
Indoor
Unit
A1
Indoor unit PCB abnormality
A5
Freeze-up protection function or high pressure control
A6
Fan motor or related abnormality
C4
Heat exchanger temperature thermistor abnormality
C7
Front panel open / close fault
C9
Room temperature thermistor abnormality
Outdoor
Unit
A5
Freeze-up protection control
E1
Outdoor unit PCB abnormality
E5
OL activation (compressor overloaded)
E6
Compressor lock
E7
DC fan lock
E8
Input over current detection
F3
Discharge pipe temperature control
F6
High pressure control in cooling
H0
Compressor sensor system abnormality
H6
Position sensor abnormality
H8
CT or related abnormality
H9
Outdoor air thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Heat exchanger thermistor or related abnormality
J8
Liquid pipe thermistor or related abnormality
J9
Gas pipe thermistor or related abnormality
L3
Electrical box temperature rise
L4
Radiation fin temperature rise
L5
Output over current detection
P4
Radiation fin thermistor or related abnormality
Summary of Contents for F-Series
Page 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Page 11: ...Introduction SiBE12 713 x ...
Page 47: ...Specifications SiBE12 713 36 Specifications ...
Page 113: ...Control Specification SiBE12 713 102 Function and Control ...
Page 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Page 235: ...Instruction SiBE12 713 224 Operation Manual ...
Page 297: ...Check SiBE12 713 286 Service Diagnosis ...
Page 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...