Setpoint/Sub-Menu
Default
Range
Description
Apply Changes=
No
No, Yes
Reboot of the controller to apply the changes made
DHCP=
Off
Off,On
Enable or disable the DHCP (Dynamic Host Configuration Protocol)
Act IP=
-
-
Actual IP address
Act Msk=
-
-
Actual Subnet mask
Act Gwy=
-
-
Actual Gateway
Gvn IP=
-
-
Given IP address (it will become the active) if the DHCP = Off
Gvn Msk=
-
-
Given Subnet mask
Gvn Gwy=
-
-
Given Gateway
Prim DNS=
-
-
Primary DNS
Sec DNS=
-
-
Secondary DNS
Host Name=
-
-
Name of the controller
MAC=
-
-
MAC address of the controller
4.3 View/Set Circuit
In this section it is possible to select between the available circuits and access data available for
the circuit selected.
Setpoint/Sub-Menu
Default
Range
Description
Circuit #1
Menu for Circuit #1
Circuit #2
Menu for Circuit #2 (if present)
The submenus accessed for each circuit are identical but the content of each of them reflects the
status of the corresponding circuit. In the following the submenus will be explained only once. If
only one circuit is available the item Circuit #2 in the above table will be hidden and not accessible.
Setpoint/Sub-Menu
Default
Range
Description
Settings
Link to circuit settings
Circuit Status=
Off:
Ready
Off:
Cycle Timer
Off:
All Comp Disable
Off:
Keypad Disable
Off:
Circuit Switch
Off:
Alarm
Off:
Test Mode
Off: Low Prs Pause (W/C units)
Run:
Preopen
Run:
Pumpdown
Run:
Normal
Run:
Evap Press Low
Run:
Cond Press High
Run:
High Amb Limit (A/C units)
Run:
Defrost (A/C units)
Status of the circuit.
Circuit Cap=
0.0%
-
Circuit Capacity
Circuit Mode=
Enable
Enable
Disable
Circuit keypad enabling
Evap Pressure=
-
-
Evaporating Pressure
Cond Pressure=
-
-
Condensing Pressure
Evap Sat Temp=
-
-
Evaporating saturated temperature
Cond Sat Temp=
-
-
Condensing saturated temperature
Suction Temp=
-
-
Suction Temperature
Suction SH=
-
-
Suction Superheat
Evap Approach=
-
-
Evaporator Approach
Cond Approach=
-
-
Condenser Approach
EXV Position=
-
-
Expansion valve position
VFD Speed
0%
0-100%
Fan Speed (A/C only)
4.3.1 Settings
This page resumes the status of the circuit.
Setpoint/Sub-Menu
Default
Range
Description